Data Sheet

2 | AUTOMATION.CROUZET.COM 05/2018 Millenium Evo expansion
Weight Without packing: 105 g
With packing: 145 g
Dimensions Without packing: 60.4 x 90 x 60.3 mm / 2.37 x 3.54 x 2.37 inch
With packing: 93 x 103 x 65 mm / 3.66 x 4.06 x 2.56 inch
Supply
Nominal voltage Powered by the controller
Max. absorbed power 2.5 W
Inputs
Digital 24 VDC and analog inputs 12 bits / 10 V & 11 bits / 0-20 mA - 6 inputs from I1 to I6 (from I1 to I4 Analog)
Input used as digital input (power off state)
Input voltage 24 VDC (-15% / +20%)
Input current 1.5 mA @ 20.4 V
1.7 mA @ 24 V
2.1 mA @ 28.8 V
Input impedance 13.9 kΩ
Logic 1 voltage threshold ≥ 11 VDC
Making current at logic state 1 ≥ 0.8 mA
Logic 0 voltage threshold ≤ 8 VDC
Release current at logic state 0 ≤ 0.5 mA
Response time 1 to 2 cycle times
Sensor type Contact or 3-wire PNP
Conforming to IEC/EN 61131-2 Type 1
Input type Resistive
Isolation between power supply and inputs None
Isolation between inputs None
Protection against polarity inversions No
Status indicator On LCD screen
Cable length ≤ 30 m
Input used as 0-10 V analogue input
Measuring range 0 → 10 V
Input impedance 13.9 kΩ
Maximum value without destruction 28.8 VDC max
Input type Common mode
Resolution 12 bit / 10V
Value of LSB 2.45 mV
Conversion time Controller cycle time
Maximum error at 25°C (77°F) ± 1.5 % of full scale
Maximum error at 55°C (131°F) ± 2 % of full scale
Repeat accuracy at 55°C (131°F) ± 0.8 %
Isolation between analogue channel and power supply None
Protection against polarity inversions Yes for voltage ≤ 10 V
Potentiometer control 2.2 kΩ / 0.5 W (recommended), 10 KΩ max.
Cable length ≤ 10 m with shielded twisted cable (sensor not isolated)
Input used as 0-20 mA analogue input
Measuring range 0 → 20 mA (4 → 20 mA by the application)
Input impedance 245 Ω
Maximum value without destruction 30 mA max
Input type Common mode
Resolution 11 bit (normalized at 0 - 2000) / 20 mA
Value of LSB 10 µA
Conversion time Controller cycle time
Maximum error at 25°C (77°F) ± 2 % of full scale