4 | AUTOMATION.CROUZET.COM 06/2018 Logic Controller
XBP24 XBP24-E XDP24 XDP24-E
Status indicator No On LCD screen
Cable length ≤ 30 m
Input used as analog input
Measuring range 0 → 10 V, 0 → V power supply or Voltmeter
Input impedance 11.6 kΩ
Maximum value without destruction 28.8 VDC max
Input type Common mode
Resolution 12 bit at maximum input voltage (10 bit at 10V)
Value of LSB 7.03 mV
Conversion time Controller cycle time
Maximum error in 0-10V mode ± 3.5 % of full scale at 25°C (77°F)
± 5 % of full scale at 55°C (131°F)
Maximum error in 0-V power supply mode ± 5 % of full scale at 25°C (77°F)
± 6.2 % of full scale at 55°C (131°F)
Repeat accuracy at 55°C (131°F) ± 2 %
Voltmeter From 0 to 30.5 V, 5%
Isolation between analogue channel and
power supply
None
Protection against polarity inversions Yes
Potentiometer control 2.2 kΩ / 0.5 W (recommended), 10 KΩ max.
Cable length ≤ 10 m with shielded twisted cable (sensor not isolated)
Digital 24 VDC - 4 inputs from ID to IG
Input voltage 24 VDC (-15% / +20%)
Input current 1.5 mA @ 20.4 V
1.7 mA @ 24 V
2.1 mA @ 28.8 V
Input impedance 13.9 kΩ
Logic 1 voltage threshold ≥ 11 VDC
Making current at logic state 1 ≥ 0.8 mA
Logic 0 voltage threshold ≤ 8 VDC
Release current at logic state 0 ≤ 0.5 mA
Response time 1 to 2 cycle times
Sensor type Contact or 3-wire PNP
Conforming to IEC/EN 61131-2 Type 1
Input type Resistive
Isolation between power supply and inputs None
Isolation between inputs None
Protection against polarity inversions No
Status indicator No On LCD screen
Cable length ≤ 30 m
Outputs
6 A relay output - 2 outputs from O1 to O2
Breaking voltage 250 VAC max
Breaking current 6 A
Derating: UL: ≥ 45°C (113°F): 4A max
Maximum breaking current in the common IEC @ 25°C (77 °F): 12 A
IEC @ 60°C (140 °F) or UL: 10 A
Mechanical life 5 000 000 operations (cycles)