Data Sheet
| Logic Controller | 3 | AUTOMATION.CROUZET.COM | 09/2018
XBP24 XBP24-E XDP24 XDP24-E
Clock drift Drift < 12 min/year (at 25 °C (77 °F))
6 s / month (at 25 °C (77 °F) with user-denable correction of drift).
Synchronizable by network
Timer block accuracy 0.5 % ± 2 cycle time
Start up time on power up < 8 s base alone, < 5 s
base + 2 expansions +
1 accessory (RS485)
< 10 s base alone,
< 5 s base +
2 expansions +
1 accessory (RS485)
< 8 s base alone, < 5 s
base + 2 expansions +
1 accessory (RS485)
< 10 s base alone,
< 5 s base +
2 expansions +
1 accessory (RS485)
Self test Test rmware integrity (checksum memory)
Stability of the internal power supply
Check the conformity of the em4 device conguration with the conguration in the application
program.
Supply
Nominal voltage
24 Vc (-15% / +20%)
Operating limits
20.4 - 28.8 Vc
Immunity from micro power cuts ≤ 1 ms (repetition 20 times)
Max. absorbed power
3.8 W @ 24 Vc,
5 W @ 28.8 Vc,
1.5 W @ 24 Vc I/O
OFF
4.8W @ 24 Vc,
6.2 W @ 28.8 Vc,
1.5W @ 24 Vc I/O
OFF
4W @ 24 Vc,
5.3 W @ 28.8 Vc, -
0.3 W backlight OFF
1.5W @ 24 Vc (I/O +
backlight) OFF
5W @ 24 Vc,
6.5 W @ 28.8 Vc, -
0.3 W backlight OFF
1.5W @ 24 Vc (I/O +
backlight) OFF
Protection against polarity inversions Yes
Power monitoring Yes and value available through the application "FB Status", 1/10V, 5%.
Inputs
Digital and high speed digital inputs 24 Vc - 4 inputs from I1 to I4
Input used as digital input
Input voltage
24 Vc (-15% / +20%)
Input current 1.8 mA @ 20.4 V
2.1 mA @ 24 V
2.5 mA @ 28.8 V
Input impedance 11.6 kΩ
Logic 1 voltage threshold
≥ 15 Vc
Making current at logic state 1 ≥ 1.3 mA
Logic 0 voltage threshold
≤ 10 Vc
Release current at logic state 0 ≤ 0.8 mA
Response time 1 to 2 cycle times
Sensor type Contact or 3-wire PNP
Conforming to IEC/EN 61131-2 Type 1
Input type Resistive
Isolation between power supply and inputs None
Isolation between inputs None
Protection against polarity inversions Yes
Status indicator No On LCD screen
Cable length ≤ 100 m
Input used as high speed digital input
Maximum counting frequency 3 channels encoder (I1, I2, I3): 5 kHz*
2 independent counters (I1, I2) (I3, I4) (Cumul, IND, DIR): 2 channels: 10 kHz*,
4 channels: 5 kHz*,
2 independent counters (I1, I2) (I3, I4) (PH, PH2): 2/4 channels: 5 kHz*
4 independent counters (I1, I2, I3, I4) (Up/Down): 1 channel: 15 kHz*, 2 channels:
10 kHz*, > 2 channels: 5 kHz*
* with a time cycle ≤ 10 ms and a ton / toff = 50% ± 5%, level 0 < 2V and level 1 > 20.4V
Other functions 4 tachometers (I1, I2, I3, I4 )
Cable length ≤ 3 m with shielded twisted cable