Instruction manual

Menu 4b.1
Manually set
AMP2 NOM=.XXX A
R
This menu is entered only if “N” is selected from menu 8a. This allows the user to manually enter a nominal
value for AMP2 current. Push the PROGRAM/EXECUTE switch to go to the next menu.
Menu 4c
AMP2 WINDOW=10% R
Use the up and down switches to set the allowable operating range of AMP2 current. This percentage is the
amount of positive or negative deviation from the nominal value before AMP2 alarm is tripped. Push the
PROGRAM/EXECUTE switch to go to the next menu.
Menu 5
REMOTE RS232
INTERFACE
R
Use the up and down switches to scroll to the desired interface (RS232, RS422, RS485). Use the LEFT/RIGHT
switch to move the cursor to R, then push PROGRAM/EXECUTE switch to jump to the SAVE SETTINGS
menu.
Menu 6
ADDRESS=00R
Use the up and down switches to set the RS485 address of the unit. This address is only applicable when
RS485 is the selected remote interface. The address is used if multiple units are connected in a multidrop
configuration. Use the LEFT/RIGHT switch to move the cursor to R, then push PROGRAM/EXECUTE switch
to jump to the SAVE SETTINGS menu.
Save Menu
SAVE SETTINGS Y/N
Select “Y” to save any changes made in the previous menus. Select “N” to revert back to the previous settings.
2.5.4 Alarm Indications
An alarm condition will occur if AMP1, AMP2, or AMP3 draw current that falls outside of their respective
current windows (when connected properly).
2082-14x-47 Manual, Rev. B Page 24 12/19/13