Instruction manual

Menu 3b.1
Manually set
AMP1 NOM=.XXX A
R
This menu is entered only if “N” is selected from menu 7a. This allows the user to manually enter a nominal
value for AMP1 current. Push the PROGRAM/EXECUTE switch to go to the next menu.
Menu 3c
AMP1 WINDOW=10% R
Use the up and down switches to set the allowable operating range of AMP1 current. This percentage is the
amount of positive or negative deviation from the nominal value before AMP1 alarm is tripped. Push the
PROGRAM/EXECUTE switch to go to the next menu.
Menu 4
SET AMP2 Y/N
WINDOW
R
If “Y” is selected then the next sequence of menus prompt the user to either automatically or manually set the
high and low current values that will trip AMP2 alarm. Push the PROGRAM/EXECUTE switch to go to the
next menu. Use the LEFT/RIGHT switch to move the cursor to R, then push the PROGRAM/EXECUTE
switch to jump to the SAVE SETTINGS menu.
Menu 4a
AMP2 NOM=.XXX
AMP2 ACT=.XXX
R
This menu is simply an indication of the present value of the nominal AMP2 current, as well as the actual
measured value of AMP2 current. Press PROGRAM/EXECUTE to proceed.
Menu 4b
Set to actual
AMP2=.XXX A Y/N
R
Select “Y” to accept the presently measured value of AMP2 current as the nominal value. Select “N” to
manually enter a nominal value of AMP2 current. The nominal current value is used as a reference from which
the high and low current thresholds are derived. Push the PROGRAM/EXECUTE switch to go to the next
menu.
2082-14x-47 Manual, Rev. B Page 23 12/19/13