Instruction manual

1.5.3 Commands Table 1.2 lists the commands for the 2082-14x-47 and briefly describes them.
After a command is sent the 2082-14x-47 sends a return “>” indicating the command has been
received and executed.
General Command Format - The general command format is {aaCND...}, where:
{ = start byte
aa = address of unit (only used if in RS485 mode, option -Q only)
C = 1 character, either C (command) or S (status)
N = 1 character command or status request
D = 1 character or more of data (depends on command)
} = stop byte
* PLEASE NOTE: The two character {aa}(00-31) prefix, in the table below,
should be used ONLY when R
S-485, (OPTION-Q), is selected.
Table 1.2 2082-14x-47 Commmands
Commands
Command Syntax* Description
Set AMP1 Nominal Value {aaC1xx} where:
or {aaC1} • xx = 10 (0.100A) to 50 (0.500A)
• NOTE: Omit xx to set nominal value to currently measured value
Set AMP2 Nominal Value {aaC2xx} where:
or {aaC2} • xx = 10 (0.100A) to 50 (0.500A)
• NOTE: Omit xx to set nominal value to currently measured value
Set AMP1 Window {aaC4xx} where:
• xx = 10 (10%) to 30 (30%) in increments of 5
Set AMP2 Window {aaC5xx} where:
• xx = 10 (10%) to 30 (30%) in increments of 5
Set Local/Remote {aaC8x} where:
• x = 0 for LOCAL mode, 1 for REMOTE mode
Set Auto/Manual {aaC9x} where:
• x = 0 for AUTO mode, 1 for MANUAL mode
Set Switch Position {aaCAx} where:
2082-141:
• x = 1 to set to:1 to 1, 2 to 2
• x = 2 to set to: 2 to 1,1 to 2
2082-142:
• x = 1 to set to: 1 to 1, 2 to 2
• x = 2 to set to: 3 to 1, 2 to 2
• x = 3 to set to: 1 to 1, 3 to 2
• NOTE: The unit will ignore the set switch position command
when not in MANUAL mode.
2082-14x-47 Manual, Rev. B Page 13 12/19/13