Instruction manual

MODEL 1582-71/72 RF Switch
1.0 General
1.1 Equipment Description
The 1582-71 provides Auto, Manual or Remote relay switching between CH1 and CH2 RF signals. Alarm
conditions on CH1 and CH2 are either a contact closure to ground or an open (selectable). The logic controls
two separate RF switches, X and Y. The 1582-72 has two independent switches. Switching logic can be
selected as follows:
1) CH1 Prime Mode - Switches from CH1 to the CH2 only if CH1 alarms and CH2 is good. Switches back
when CH1 no longer in alarm or both CH1 and CH2 are bad.
2) Latch to CH2 Mode - Switches to CH2 if CH1 alarms and CH2 is good. Latches to CH2. Push Manual
Reset or ground Remote Reset pin to return to CH1 if it has no alarm.
3) Minimum AUTO switching, Initial Channel Select ( ICS) Mode- Switch stays on channel last selected by
Manual or Remote selection after return to AUTO. AUTO switching occurs only if current channel alarms and
other channel clear.
When power is lost and on power up (as alarms at power up dictate), channel 1 is selected. The Manual Select
switch and (when in AUTO) contact closures to Remote Select pins, select CH1 or CH2 independent of
alarms. LEDs indicate alarms. LEDs and closures to ground indicate switch conditions for CH1, CH2 and
REMOTE or MANUAL operation. Redundant power supplies