1.0 GENERAL
PDC series systems are configurable, digital, microprocessor based, controllers for use in non-hazardous (non-explosion rated) environments
for commercial and industrial applications. They are available in several basic configurations. One to eight analog channels, one to sixteen
digital channels, one to thirty-two digital channels, one to sixty-four digital channels, one to ninety-six digital channels, one to one hundred and
twenty-eight digital channels.
NOTE: Only the first eight system channels can be utilized for analog inputs.
A basic system provides one common set of LED indicating lights for “Power”, “Fail”, “Low (Warning) Gas Alarm”, “Mid Gas Alarm, “High Gas
Alarm”, an integral audible alarm with silence push-button, scrolling, backlit, 2-line LCD digital display, eight dry contact relays, user
configurable circuit and RS485, 4-wire “multi-drop” wiring. An eight channel version is also available for use with conventional analog
transmitters.
A good selection of electrochemical, MOS (Metal Oxide Semi-conductor) solid-state, and catalytic sensor / transmitters (digital and analog)
are available for use within the PDC series controllers.
2.0 CONTROLLER SPECIFICATIONS
Physical: Standard:
a) Dimensions: 12.0” Wide X 12.0” High X 4.0” Deep (311 mm Wide X 311 mm High X 106 mm
(Deep)
b) Weight: 3.49 pounds (1.585 kg)
Water/dust tight:
a) Dimensions: TBA
b) Weight: TBA
Materials: Standard: Rugged 18 gauge powder painted metal with hinged, secured key-lock door and Lexan
door label. General purpose rating.
Water/dust tight: Fiberglass reinforced polyester
Visual: a) Common set of LED indicating lights for:
* Power (green)
* Fail (red)
* Low (Warning) Gas Alarm (amber)
* Mid (Intermediate) Gas Alarm (red)
* High Gas Alarm (red)
b) Two-line, sixteen character, backlit LCD digital display for sensor/channel information,
quantitative readings and alarm status.
c) Amber colored LED relay coil status indicators (8-leads)
d) Red colored LED “ loop” indicators for analog version (8-leads)
Audible: Integral, door mounted sonalert with silence push-button. Rated 90 dB @ 10’
Environment: a) Temperature: 0 deg. C. to +40 deg. C. (32 deg. F. to 104 deg. F.)
b) Humidity: 0 to 95% non-condensing
Power: 90 to 250 VAC, 47 to 63 Hz
Current Load: Maximum allowable system current load: 1.36 Amps @ 24 VDC (power supplied to remote transmitters)
Relays: Standard: Eight only S.P.D.T. dry contact relays, rated 5 amps @ 240 VAC each.
Outputs: a) Strobe: 24VDC alarm level activated MAXIMUM 400 mA (global alarm control)
b) Auxiliary: 24VDC alarm level activated MAXIMUM 400 mA (global alarm control)