User Manual

cGas Ammonia Vent Line Transmitter - Addendum Rev. B | 2022.09
18 © 2022 All rights reserved. Data subject to change without notice.
7 MAINTENANCE
There are no serviceable elements other than the calibration instructions outlined in this
manual. There are no replaceable components except the sensor.
The cGas Ammonia Vent Line Detector requires no assembly and very little maintenance.
The transmitter should be regularly inspected and monitored for possible damaging
conditions.
If in a damp location, source of water should be shielded from continually contacting
the top of the transmitter. It is important to ensure that excess water and/or dust is
not somehow entering the enclosure and physically damaging the circuit board or
internal components.
If painting is to be conducted in the transmitter’s location the transmitter needs to be
protected from over spray.
If mounted outside in very cold temperatures (> -20°C / -4°F ), encasing the
transmitter in a suitable insulated box may be necessary
8 TROUBLESHOOTING
cGas Detector won’t power up. (blank display)
Is the power properly connected? Check the wiring connections. Refer to Wiring Connections
in the Installation Manual.
Display shows “SPAN FAULT” message.
Check all connections and possible interferences and try a complete calibration procedure
from the beginning again to see if this corrects the fault. If a second calibration does not
resolve the fault then the sensor needs to be replaced. Check to make sure the gas cylinder
isn’t empty.
Frequent, unexpected alarm signal sent to BAS/DDC.
Check to see if EMI and RF interference is causing the equipment to react this way. Refer to
EMI and RF Interference Considerations in the Installation Manual for more information.
Display shows “COMM” message. Modbus® or BACnet output signal has not been
connected properly; will also occur if no requests are being made from the controller to
the transmitter, ie addressing is not proper. Check the wiring connections and the network
settings.
Device cannot be seen by the Controller and/or the BAS / DDC on the Modbus® network.
Check the Baud rate. All devices in the network must have the same Baud rate.
Check that local area network wiring is correct, especially the A and B lines to make sure they are not
swapped between devices on the network.
Check the Modbus® ID. Each device must have a unique ID assigned to it.
Device cannot be seen by the Controller and/or the BAS / DDC on the BACnet® network.
Check the Baud rate. All devices in the network must have the same Baud rate.
Check to make sure the device has a unique ID assigned to it, the factory default is made up of the
MAC ID and the Base ID.