User Manual
Rev. B | 2022.09 cGas Ammonia Vent Line Transmitter - Addendum
© 2022 All rights reserved. Data subject to change without notice. 13
5.2 Set Calibration Gas Value
Check to make sure that the calibration gas value set in the transmitter matches the gas
concentration of the calibration gas you are using. How much gas the sensor detects is
directly related to the Calibration Gas setting and the actual concentration of calibration gas
used during calibration.
The factory default used to calibrate the cGas Ammonia Vent Line Detector prior to shipping
is 0.5 % vol (5000 ppm) air balance.
From the main display, press ENTER.
Enter passcode 3032 using the UP button and ENTER button.
Enter Password
3032
Press ENTER to access the Calibrate Menu.
Calibrate Menu
Press Enter
In the Selected Channel menu, conrm the desired channel is showing.
Selected Channel
NH3
Press the UP button to accept the displayed calibration gas value if it is correct. Or press
ENTER and change the value using the UP or DOWN buttons.
Calibration Gas
0.5% vol NH3
Calibration Gas
>0.5% vol NH3
When nished pressed ENTER and then ENTER again to conrm and ENTER to exit.
Conrm?
>0.5% vol
N
>Y
5.3 Attach Calibration Adapter with Tubing
The ammonia sensor is potted into a 5 cm / 2 in long pipe tting that protrudes from the
back of the enclosure.
Press the calibration adapter with an O-ring and two zeroing port plugs into the sensor
opening with the tubing attached.
(P/N: CET-7000-CAP)