Specifications
Current Sensor Module Crestron ST-CS
Use the following instructions to set or change the Net ID.
1. Ensure that the device requiring a Net ID change is the only Cresnet unit
connected to the control system.
2. Open the Crestron Viewport.
3. From the Viewport menu, select Functions | Set Network ID. The software
checks the baud rate and then opens the "Set Network ID" window.
4. In the "Set Network ID" window, select the device requiring a Net ID
change from the Current Network Devices text window.
5. Select the new Net ID for the device from the Choose the new network ID
for the selected device (Hex): text box.
6. Click Set ID to initiate the change. This will display the "ID command has
been sent" window.
7. In the "Command Complete" window, click OK.
8. In the Current Network Devices text window, verify the new Net ID code.
9. In the "Set Network ID" window, click Close.
NOTE: The new Net ID code may also be verified by selecting Diagnostic | Report
Network Devices in the Viewport (alternately, select F4).
10. Repeat this procedure for each additional network device requiring a Net ID
change.
Hardware Hookup
Refer to the following hookup diagram. Other than making the power connection
last, complete the connections in any order.
CAUTION: Use only Crestron power supplies for Crestron equipment. Failure to do
so could cause equipment damage or void the Crestron warranty.
NOTE: When installing network wiring, refer to the latest revision of the wiring
diagram(s) appropriate for your specific system configuration, available from the
Downloads | Product Manuals | Wiring Diagrams section of the Crestron website
(www.crestron.com).
The following diagram shows connection to Cresnet. The threshold adjustment
procedure that follows provides the steps necessary to properly attach a device that
needs to be sensed (i.e., display device) to the ST-CS POWER A connector and
adjust the POTS. If necessary, repeat the steps and attach a second device to
POWER B.
NOTE: Do not attempt adjustments during periods of high or low power line
voltage or voltage fluctuations.
NOTE: The partial power adjustment may be used as the primary output instead of
the full adjustment if increased sensitivity is required.
8 • Current Sensor Module: ST-CS Operations Guide - DOC. 5677A