Specifications

Crestron ST-CS Current Sensor Module
ST-CS Indicators and User Adjustments
There are six LED indicators and four POTS located on the front panel of the ST-
CS. Refer to illustration and descriptions below.
ST-CS Indicators and Adjustments
POWER B
CURRENT SENSOR
CRESTRON
PWR NET
PARTIALFULL
POWER A
FULL
ST-CS
PARTIAL
PWR (Power)
This LED illuminates when 12 volts or 24 volts DC is supplied to the ST-CS.
NET
This LED illuminates when communication between the control system and the ST-
CS is established. Illumination indicates that the SIMPL program currently loaded
has a network device defined at the same network ID as the ST-CS.
FULL (POWER A & B)
These LEDs illuminate when full load threshold has been exceeded.
Clockwise 3 rotation of the 15-turn POT decreases threshold (i.e., increases
sensitivity) and changes partial load threshold, accordingly.
PARTIAL (POWER A & B)
These LEDs illuminate when partial load threshold has been exceeded.
Clockwise 3 rotation of the 15-turn POT decreases threshold (i.e., increases
sensitivity).
Setup
Identity Code
Refer to the note on page 14 for a
definition of Viewport.
All equipment and user interfaces within the network require a unique identity code
(Net ID). These codes are two-digit hexadecimal numbers from 03 to FE. The Net
ID of each unit must match an ID code specified in the SIMPL Windows program.
Refer to “Setting the Net ID in Device Settings” on page 12 for details of the SIMPL
Windows procedure.
The Net ID of the ST-CS has been factory set to 18, The Net IDs of multiple ST-CSs
in the same system must be unique. Net IDs are changed from a personal computer
(PC) via the Crestron Viewport.
NOTE: For detailed information on establishing communication between the PC
and control system, refer to “Communication Settings” on page 14. If
communication cannot be established, refer to the “Troubleshooting
Communications” section in the respective Operations Guide for the control system.
Operations Guide – DOC. 5677A Current Sensor Module: ST-CS 7