System information
Crestron 2-Series Control Systems Reference Guide
Reference Guide – DOC. 6256A 2-Series Control Systems • 135
Error Level Messages, E (continued)
MESSAGE DEFINITION
Error creating internal
signal in
Symbol/Device#.
(0029:####:0029)
Internal system error. Contact Crestron.
Error obtaining
RamFileAreaSemaph
ore.
Internal system error. Contact Crestron.
Error #### sending
packet to Slot-09.ID-
0A (0032:####:0032)
This error is a general timeout. Error –1 may be seen once before
an error issued that a device has gone offline. This error is not
typically seen in 2.004 CUZ or later; however it was more common
in older CUZ files. If Error –50 is seen for Cresnet devices, this is
typically some form of a timeout caused by problematic wiring or
devices on the same ID code. This error can still occur in later CUZ
files, although internal error recovery is greatly improved.
Error parsing integer
parameter in config
file.
Internal system error. Contact Crestron.
Error parsing string
parameter in config
file.
Internal system error. Contact Crestron.
Error reading the IP
table.
The system use not able to read the IP table. The table could be
corrupted.
Error registering
Symbol/Device#.
Ethernet Initialization
failed. Confirm
correct IP Address
and Subnet Mask.
(0054:####:0054)
The system was not able to initialize Ethernet. The most common
causes, as stated, are an invalid IP address and/or subnet mask.
Error registering
Symbol/Device#.
Make sure there is an
IP table entry for IP ID
####.
(004F:####:004F)
There is a device in the program with the given IP ID # (as given by
the Symbol/Device#), but there is no corresponding entry in the IP
table. There must be an IP table entry for the device to function
correctly.
Error registering
Symbol/Device#. No
card found at this
location.
(0052:####:0052)
The program is referencing a card in a particular slot, but there is no
card in the given slot.
Error registering
Symbol/Device#. No
ethernet card present
or ethernet is
disabled.
(0050:####:0050)
There is no Ethernet card in the system or Ethernet has been
turned off. It must be present/enabled for Ethernet devices to be
registered properly.
Error registering
Symbol/Device#.
There is already a
device at IPID ####.
(0051:####:0051)
This would not happen in standard practice, as SIMPL Windows
prevents duplicate devices at a given ID.
Error registering
Symbol/Device#.
Wrong card found at
this location.
(0053:####:0053)
The program is referencing a card in a given slot, but that card is
not in the slot (a different card is). There are occasions where a
different card may be in the slot (different than what the program
expects) but no error is issued, such as a CNXCOM-2 card defined
in the program and a C2COM-3 card is present.
(continued on next page)