System information
Reference Guide Crestron 2-Series Control System
124 • 2-Series Control Systems Reference Guide – DOC. 6256A
Warning-Level Messages (continued)
MESSAGE DEFINITION
Could not solve logic
within #### waves.
(0004:####:0004)
An entire solution must be no greater than a specific number of
waves. Currently, this is set to 1000 waves. If there is circular logic
in a program (i.e. logic that loops back on itself and keeps
changing) then this message can be issued.
Ethernet Device name
Not Responding (IP =
nn.nn.nn.nn). Device
Offline
A timeout has occurred trying to transmit data to a CIP device. The
device is offline.
EtherTask: DHCP
failed (Status = -290)
Processor was unable to obtain a DHCP address from a DHCP
server. Possible causes are:
1. The processor is not connected to a LAN. When using a
Ethernet card with two LAN ports (such as the C2ENET-2
card), the LAN should be connected to LAN A when using
a DHCP server.
2. There is no DHCP server running on the network.
3. The DHCP server has no more addresses to give out.
CIP Node Offline: ID
nn, IP = nn.nn.nn.nn
A timeout has occurred trying to transmit data to a CIP device. The
device is offline.
Disk Insertion error.
Please try again.
An error occurred initializing the compact flash. Remove the disk
and re-insert it.
Invalid delay time of
zero in Logic Wave
Delay
Symbol/Device#.
Assuming value of
one (1).
(002A:####:002A)
A logic wave delay must be timed for at least one wave. This
message indicates that the symbol had a value of 0 put in it. Under
this condition, the system assumes one wave delay.
Invalid format #### in
Serial to Indirect Text
Symbol/Device#.
Assuming no format.
(0040:####:0040)
The Serial Send only has a specific number of formats (refer to the
SIMPL Windows help file). If a format that does not exist is
specified, it defaults to format 0d (no format).
Invalid mode ####
specified for Text
Append symbol
Symbol/Device#,
assuming mode ####.
(005A:####:005A)
The Text Append symbol only has specific modes, and an invalid
mode was specified on the input analog. If an invalid analog input
is given for the mode, the specified mode is used instead. Consult
the SIMPL Windows help file for specifics on the Text Append
symbol.
Invalid post-processor
data.
(0003:####:0003)
Internal system error. Contact Crestron.
Invalid pulse time of
zero in Logic Wave
Pulse
Symbol/Device#.
Assuming value of
one (1).
(0055:####:0055)
Since there is no such thing as a 0 time pulse, the symbol converts
a “0” time logic wave pulse into a 1 logic wave pulse. This would be
the same as if the user typed 1d in the parameter field of the given
logic wave pulse symbol.
Invalid Slave
configuration packet
received by
Symbol/Device#
(Packet Printout).
(0060:####:0060)
Internal system error. Contact Crestron.
(continued on next page)