System information
Crestron 2-Series Control Systems Reference Guide
Reference Guide – DOC. 6256A 2-Series Control Systems • 123
Appendix D: Error Message Definitions
Definitions for each error message are logically grouped first by level (Notice,
Warning, Error, and Fatal) and then alphabetically. Refer to the following tables.
NOTE: Words or phrases shown in italics are replaced in the actual message with
specific information. For example, Symbol/Device# might be replaced by something
such as S-5 or Slot-9.ID-06.
NOTE: Errors with the “Internal system error. Contact Crestron.” Definition cannot
be resolved without assistance from a Crestron customer service representative.
Refer to “Further Inquiries” on page 80 for details.
Notice-Level Messages
The following table lists notice-level messages. A notice-level message is displayed
when an event has occurred that is noteworthy, but will not affect program operation.
Notice-Level Messages
MESSAGE DEFINITION
CIP device nn: back
ONLINE.
CIP device nn has come back on line.
Compact Flash
Initialized.
The compact flash has been initialized and is ready for use.
Compact Flash
Removed.
The compact flash was extracted from the system.
Link established on
LAN A/B.
The system detected a new Ethernet link on LAN A or B.
No previously defined
Serial RAM symbol
for FIFO Queue
Symbol/Device#.
(001A:####:001A)
If the FIFO Queue (QUE) symbol is using serial data, it requires a
Serial RAM symbol defined before it to operate. The FIFO Queue
symbol is sometimes used for a push/pop stack (queuing up
numbers, not names) and the Serial RAM is not required for this;
however this is a rare usage. As such, the message can be ignored.
No Program Present.
(001D:####:001D)
This message is issued when the system starts and no program is
loaded.
Warning-Level Messages
The following table lists warning-level messages. A warning-level message is
displayed when an event has occurred that could affect program operation, but the
program can still run normally.
Warning-Level Messages
MESSAGE DEFINITION
Could not allocate
memory for Serial
Binary to Hex
symbol/device#.
(0039:####:0039)
Internal system error. Contact Crestron.