22 • Professional Automation Control System: PAC2 Operations Guide – Doc. 5941A
4. Power down the PAC2.
5. While powering up the PAC2, press and hold Alt and K on the keyboard
until the following text (or similar) appears in Viewport:
System Monitor [v1.001 (0001)]
12-19-01 16:25:23 32 MB RAM, 4MB FLASH
CS>
NOTE: After this, the baud rate can be increased to 115200 (for faster
communication) by pressing F8 on the keyboard and then selecting 115200 from the
“Set Baud Rate” window.
6. At the Viewport prompt, type erase and press Enter. The following text
appears in Viewport.
CS>erase
->25%->50%->75%->100%
Done
CS>
7. Press Alt and O (not zero) on the keyboard. The “Open” window appears.
8. Find and select the correct firmware file (.CUZ) and click Open.
9. Once “Completed Successfully” appears in Viewport, type quit at the
Viewport prompt and press Enter.
Serial Communication Difficulties with Other
Devices Connected to the PAC2
It is possible to determine if a communication problem is in the PAC2 or in the
device itself by using passthrough mode. Passthrough mode allows data to pass
directly from the COMPUTER port to the selected COM port on a Cresnet or
Ethernet device (such as ST-COM or CEN-COM), effectively “passing through” the
control system. While passthrough mode is running, the program currently in
memory is suspended and does not execute. When passthrough mode is exited, the
program resumes operation.
Entering passthrough mode for one of the internal COM ports reinitializes it, which
clears the data for that port. The COM analyzer also functions while the unit is in
passthrough mode.
Passthrough mode is accessed from the Crestron Viewport by selecting Functions |
Enter Passthrough Mode (CNX / 2-Series only). The window, shown after this
paragraph, is used to select the port configuration for passthrough mode. For more
information, refer to “Remote Menu” in the Viewport Help files.