Specifications

infiNET™ DIMMERS
Testing
NOTE: The device may be warm to the touch during
operation. This is normal.
Test the installation by setting the dimmer’s mode
selection switch (shown in the following diagrams) to the
“RUN” position and perform either of the following steps
(depending on the dimmer model).
Parts of CLW-DIM1RF and -DIMS1RF
RUN
SET OFF
Button
Mode Selection Switch
Parts of CLW-DIM4RF, -DIMS4RF
Button 2
Mode Selection Switch
Button 4
Button 3
Button 1
OFFSET
RUN
Testing a -DIM1RF or-DIMS1RF
With the mode selection switch in the “RUN” position,
tap the top of the button to turn on the load. Tap the
bottom of the button to turn off the load.
For detailed operating instructions, refer to the latest
revision of the infiNET Dimmers Operations Guide (Doc.
6396) which is available from the Crestron website.
Testing a -DIM4RF or -DIMS4RF
With the mode selection switch in the “RUN” position,
tap the Button 1 to turn on the load. Tap Button 1 again to
turn off the load.
For detailed operating instructions, refer to the latest
revision of the infiNET Dimmers Operations Guide (Doc.
6396) which is available from the Crestron website.
Testing a -SLVD1RF
Tap the top of the button to turn on the load. Tap the
bottom of the button to turn off the load. It will emulate
the RUN mode of the -DIMS1RF (even if connected to a
-DIMS4RF) unless the mode selection switch of the
master is set to “OFF”. For more information, refer to the
latest version of the infiNET Dimmers Operations Guide
(Doc. 6396) which is available from the Crestron website.
infiNET Network
Before an infiNET dimmer can be used in a controlled
lighting system, it must first be acquired to a
C2N-MNETGW gateway that is connected to a Cresnet
network.
NOTE: The -DIM1RF, -DIM4RF, -DIMS1RF, and
-DIMS4RF can also work as stand-alone wall box
dimmers without being acquired by a C2N-MNETGW.
NOTE: A dimmer can be acquired to only one gateway.
To acquire a -DIM1RF/-DIM4RF/-DIMS1RF/-DIMS4RF
to a C2N-MNETGW, perform the following:
1. Put the C2N-MNETGW in the Acquire mode,
from the unit itself or from Crestron Toolbox™,
as described in the latest revision of the
C2N-MNETGW Operations Guide (Doc. 6317)
which is available from the Crestron website or
the Crestron Toolbox help file.
NOTE: In an environment where multiple
gateways are installed, only one gateway should
be in the Acquire mode at a time.
2. Place the -DIM1RF/-DIM4RF/-DIMS1RF/
-DIMS4RF into the Acquire mode by doing the
following:
a. Move the mode selection switch
(located under the LED) to the “OFF”
position.
b. Press and hold the top or bottom of the
button on the -DIM1RF/-DIMS1RF or
any button on the -DIM4RF/
-DIMS4RF.
c. While holding the button, slide the
mode selection switch to the “RUN”
position.
d. Hold the button for approximately five
seconds until the LED flashes HIGH
once. Immediately release the button
after the LED blinks to start the
switch’s Acquire mode.
6 infiNET™ Wall Box Dimmer : CLW-DIM1/4RF, DIMS1/4RF, & SLVD1RF Installation Guide – DOC. 6292C