Installation guide
Crestron CHV-TSTATEX infiNET EX Thermostat
Operations & Installation Guide – DOC. 6989C infiNET EX Thermostat: CHV-TSTATEX
•
27
Setup Mode Parameters/Functions (Continued)
PARAMETER/
FUNCTION
CODE VALID VALUES
DEFAULT
VALUE
NOTES
Perform Aux Heat Call
Test (Toggle)
(appears only on Heat
pump and Dual-Fuel
Heat pump systems)
A Not started/Aux call
off (--)
Aux call on (on)
(also, “A” icon turns
on)
N/A Same as above, for testing aux
heat output
Perform Fan Call Test
(Toggle)
F Not started/Fan call
off (--)
Fan call on (on)
(also, “F” icon turns
on)
N/A Same as above, for fan;
Note that only the fan relay can be
activated for a fan call test
Perform Self Test St Not started (--)
In progress
(flashing --)
Finished, self test ok
(00)
Finished, self test
failed (E#, where #
represents an error
code)
N/A Refer to “Self-Test Results” which
starts on page 28 for details
Verifying Communication Status
To verify communication status, enter the Setup mode as described in “Basic Setup”
on page 21. Press MODE until the AC, UA or CC function is displayed. Press
or
on the CHV-TSTATEX to verify the communication status.
Communication Error Codes
STATUS/
ERROR
CODE
MEANING FOR
ACQUIRE “AC”
MEANING FOR
UNACQUIRE “UA”
MEANING FOR
COMMUNICATION
CHECK ”CC”
00 Success Success No problems found
E1 No gateway found Failed or no previous
gateway information was
present
No gateway information
present
E2 GW found but rejected
device
N/A N/A
E3 Radio operation not
available
Radio operation not
available
Radio operation not available
E4 N/A N/A N/A
E5 N/A N/A N/A
E6 N/A N/A Network communication not
possible
E7 N/A N/A Device not joined to a
gateway