Installation guide
infiNET EX Thermostat Crestron CHV-TSTATEX
26
•
infiNET EX Thermostat: CHV-TSTATEX Operations & Installation Guide – DOC. 6989C
Setup Mode Parameters/Functions (Continued)
PARAMETER/
FUNCTION
CODE VALID VALUES
DEFAULT
VALUE
NOTES
InfiNET EX ID
(RF ID)
id 01 and 03 – FE 01 Sets the infiNET EX ID. Crestron
Studio (or SIMPL Windows)
restricts infiNET EX devices to an
ID range of 03 – 20
infiNET EX Sleep Time SL Short (S) or Long (L) L Indicates thermostat update rate;
Setting for fewer updates (L)
conserves battery power
Start infiNET EX
Acquire
AC Not started (--)
In progress
(flashing --)
Finished, found GW
(00)
Finished, could not
find GW (E#, where
# represents an error
code)
N/A Refer to “Verifying Communication
Status” which starts on page 27 for
details
Unacquire Gateway UA Not started (--)
In progress
(flashing --)
Finished, success
(00)
Finished, failed (E#,
where # represents
an error code)
N/A Refer to “Verifying Communication
Status” which starts on page 27 for
details
Communications
check
CC Error (E# - where #
is a number from 0 to
7)
No problems (00)
N/A Refer to “Verifying Communication
Status” which starts on page 27 for
details
Check Battery Life bA Not started (--)
Estimated remaining
battery life (0 – 99)
N/A Gives estimated remaining battery
life in percent
Restore Factory
Defaults
Fd Not started (--)
In progress (blank or
flashing --)
Finished (00)
Button not held long
enough (Er)
N/A Restores all setup parameters to
their default settings;
To prevent accidentally performing
this action, press and hold either
the or button for three
seconds for this function to execute
Perform Heat Call Test
(Toggle)
H Not started/Heat call
off (--)
Heat call on (on)
(also, “H” icon turns
on)
N/A Tests the heat call output.
Bypasses short-cycle timers;
Useful for technician system testing;
Note that calling the heat may
activate other relays in the
thermostat as required, such as the
fan output for heat pump or
dual-fuel types
Perform Cool Call Test
(Toggle)
C Not started/Cool call
off (--)
Cool call on (on)
(also, “C” icon turns
on)
N/A Tests the cool call output;
Bypasses short-cycle timers;
Useful for technician system
testing;
Note that calling the cooling may
activate other relays in the
thermostat as required, such as the
fan output
(Continued on following page)