Installation guide

Crestron CHV-TSTATEX infiNET EX Thermostat
Operations & Installation Guide DOC. 6989C infiNET EX Thermostat: CHV-TSTATEX
23
Advanced Setup
Setup Mode
After the CHV-TSTATEX is installed, it is necessary to set it up for a particular
heating/cooling system. Please note that some of the setup parameters listed below
are not always shown since they are dependent upon other thermostat settings. Refer
to Setup Mode Parameters/Functions” which starts on page 24 for details.
Place the CHV-TSTATEX in the Setup mode by doing the following:
1. Press and hold the FAN button.
2. While the FAN button is being held, press and hold the
and buttons
simultaneously.
3. Hold all three buttons for 5 seconds, after which the unit enters Setup mode.
Once in Setup mode, the display indicates the currently selected setup
parameter/function. Press and release the MODE button quickly (must be released
within one second) to change to the next parameter/function in the list.
NOTE: Holding the MODE button for more than one second resets the currently
selected parameter/function to its default value.
When setting parameters (such as when choosing between Fahrenheit or Celsius
display), pressing the
or button increments or decrements the value. Value
change occurs when button is released.
When a function is selected (such as when starting an infiNET EX acquire), pressing
either
or executes the function.
To exit from Setup mode, press the FAN button on the CHV-TSTATEX.
CHV-TSTATEX LCD Display (Setup Mode)
NOTE: When the CHV-TSTATEX is in Setup mode the large 7-segment displays
show the current setup parameter/function. The small 7-segment displays show the
current value for the selected setup parameter, if applicable, or it displays “—” when
a function is selected. All other display elements are hidden (refer to “
LCD Display
which starts on page 32
).
MODE
FAN
Skips to Next Setup
Parameter/Function
Indicates Current Setup
Parameter/Function
Indicates Current Value for
selected Setup Parameter
Exits Setup Mode
Adjust Current Setup
Parameter/Function Value