infiNET EX Thermostat: CHV-TSTATEX Operations & Installation Guide DOC. 6989C
2. Ensure the unit is in Setup mode (refer to “Basic Thermostat Setup” which starts
on page 21 or “Setup Mode” which starts on page 23) and that Acquire mode
(AC) is selected.
3. Press MODE
until the infiNET EX IDfunction is displayed (id).
Use
and to choose the infiNET EX ID.
4. Press MODE until the “Start infiNET EX Acquire” function is displayed (AC).
5. Press
or on the CHV-TSTATEX to start the acquire process: The display
shows flashing “ (in progress). When finished, the display shows 00
(finished, found gateway) or E# (finished, could not find gateway), where #
represents an error code.
6. Once all devices have been acquired, take the CEN-RFGW-EX out of Acquire
mode by pressing its ACQUIRE button. Press FAN on the thermostat to exit
Setup mode.
NOTE: The acquire process can take up to 15 seconds. The acquire process cannot
be aborted.
NOTE: “E1” indicates that search time has expired and no gateway was found. To
enable the channel, refer to “Start infiNET EX Acquire” in “Setup Mode
Parameters/Functions” which starts on page 24
.
Leaving an infiNET EX Network
To leave a network, press and hold the FAN, and buttons simultaneously for
five seconds. Press MODE until the unacquire function is displayed (UA). Press
or
on the CHV-TSTATEX to start the unacquire process. Refer toVerifying
Communication Statuson page 27 for a list of codes displayed once the process is
completed. Press FAN on the thermostat to exit Setup mode.