Installation guide

Crestron CHV-TSTATEX infiNET EX Thermostat
Operations & Installation Guide DOC. 6989C infiNET EX Thermostat: CHV-TSTATEX
9
Setup
Identity Code
Every CHV-TSTATEX communicating via RF with a Crestron control system
through a CEN-RFGW-EX wireless gateway or with an MC3 3-Series Control
System requires a unique RF ID. The RF ID is a two-digit hexadecimal number that
can range from 03 to FF. The RF ID of the unit, set using Crestron Toolbox™, must
match the RF ID specified in the Crestron Studio or SIMPL Windows program.
Supplied Hardware
The hardware supplied with the CHV-TSTATEX is listed in the following table.
Supplied Hardware for the CHV-TSTATEX
DESCRIPTION PART
NUMBER
QUANTITY
Screws, Zinc, Phillips, Pan Head, #06-32 x 1” 2007251 2
Batteries, AA, Alkaline 2001050 2
Installation
NOTE: Installers should have a strong working knowledge of HVAC systems.
The location of the thermostat can affect its performance and efficiency. Install the
thermostat away from direct sunlight, drafts, doorways, skylights and windows. Also
make sure the thermostat is conveniently located for control access and setup.
Thermostats should be mounted 60 inches (~1.6 meters) above the finished floor
(HVAC industry standard). Do not mount on an exterior wall.
The following tools and hardware are required for installation:
Standard 1-gang electrical box, mounted horizontally (not supplied)
Phillips screwdriver (not supplied)
Two 1-inch pan head Phillips screws (included)
Two AA batteries (included)
Use the following procedure to install the CHV-TSTATEX in a standard,
1-gang electrical box (refer to illustration on the following page):
1. Turn HVAC system power OFF.
2. Separate thermostat front plate from rear plate. (This may require exerting
force when removing the front plate.)
3. Feed HVAC wiring from the electrical box through the hole in the center of
the rear plate so it can be connected to the proper terminals on the
CHV-TSTATEX after the thermostat is mounted.