Setup guide

Crestron IPAC-GL1 Integrated Professional Automation Computer
a. Activate each sensor displayed to test the functionality.
b. Press the soft button labeled OK to return to the Sensors section of
the Setup Menu.
Assign Sensors and Modes to
Loads
Loads can be assigned to perform a function based on a sensor input. Refer to the
“Panel Worksheet” in the latest version of the IPAC-GL1 System Planning
Worksheets when assigning loads to sensors. To assign a load and associated
function to a sensor input:
1. Open the Sensors section of the Setup Menu as described on page 39.
2. Press the soft button labeled Loads. A list of loads will be displayed.
Sensor Load Assignments
SelectMode Edit OK
Sensor Load Assignment
L1.1 = Int (On/Off)
L1.2 = C0.1 (Off Only)
L1.3 = ---
Copy
To assign a sensor:
a. Turn the selection knob to highlight a load and press the ENTER
button or the soft button labeled Edit.
Assign a Sensor
Set
Sensor Load Assignment
L1.1 = [Int] (On/Off)
L1.2 = C0.1 (Off Only)
L1.3 = ---
SelectSet
A load’s sensor assignment and function can be copied to other
loads. For more information, refer to “Copy/Paste Sensor ” on page
46.
b. Turn the selection knob to the desired sensor and press the soft
button labeled Set. To remove a sensor assignment, turn the
selection knob until --- is displayed and press the soft button
labeled Set.
NOTE: A load can have only one sensor assigned to it.
Setup Guide – DOC. 6660B Integrated Professional Automation Computer: IPAC-GL1 45