Setup guide

Integrated Professional Automation Computer Crestron IPAC-GL1
For a sensor connected via a GLS-SIM:
Sensor Test for Sensor Connected via GLS-SIM
OK
Sensor C3.1/2 Test
IN 1: Type = N/O
Status = Active
IN 1: Type = N/O
Status = Active
SelectOK
The GLS-SIM uses DIP switches for setting the type of sensor that is
connected. Sensors can be configured as a normally open sensor (N/O),
a normally closed sensor (N/C), active high (Active Hi), or active low
(Active Lo).
DIP Switches on GLS-SIM
ON
OFF
1
2
3
4
DIP switches 1 and 2 set the sensor type for input 1 on the
GLS-SIM while DIP switches 3 and 4 set the sensor type for input 2 on
the GLS-SIM. The following table shows the settings for each sensor
type.
DIP Switch Settings for the GLS-SIM
INPUT 1 INPUT 2
SENSOR TYPE
SWITCH 1 SWITCH 2 SWITCH 3 SWITCH 4
Active High Off Off Off Off
Active Low Off On Off On
Normally Open On Off On Off
Normally Closed On On On On
For more information, refer to the latest version of the GLS-SIM
Sensor Integration Module Operations & Installation Guide (Doc.
6768) which is available for download from the Crestron website.