a. To toggle between the different types of sensors, press the soft
button labeled Type.
b. Activate the sensor to test the functionality. The status will be
displayed.
c. Press the soft button labeled OK to return to the Sensors section of
the Setup Menu.
For a sensor connected via a DIN-IO8:
Sensor Test for Sensor Connected via DIN-IO8
Type OK
Sensor D4.1-8 Test
Input: Type=Active Hi
Status = A,A,A,A,A,A,A,A
I=Inactive, A=Active
SelectOK
The DIN-IO8 inputs can be configured as:
Active HI (default): A sensor which pulls down below 1.25VDC
when inactive and which provides a voltage above 1.35VDC (and
less than or equal to 24VDC) when active. (GLS occupancy
sensors available from Crestron are of this type).
Active Low: A sensor which provides a voltage above 1.5VDC
(and less than or equal to 24VDC) when inactive and which pulls
down below 1.25VDC when active.
Normally Open (N/O): A sensor which provides an open circuit
when inactive, and a dry contact closure when active.
Normally Closed (N/C): A sensor which provides a dry contact
closure when inactive and an open circuit when active.
a. To toggle between the different types of sensors, press the soft
button labeled Type.
b. Activate the sensor to test the functionality. The status will be
displayed.
c. Press the soft button labeled OK to return to the Sensors section of
the Setup Menu.