Setup guide

Crestron IPAC-GL1 Integrated Professional Automation Computer
GLS-SIM and DIN-IO8 modules that have been identified to the IPAC are
listed as Online. If a GLS-SIM or DIN-IO8 has not been identified to the
IPAC, it is listed as Not Found.
NOTE: The Online/Not Found status does not take the state of the actual
sensors into account. For this, refer to “Test Sensors” on page 42.
Identify Sensor Modules
Every sensor module connected to the IPAC must be identified to the system. To
identify a sensor module:
1. Open the Sensors section of the Setup Menu as described on page 39.
2. Turn the selection knob to highlight a sensor that is listed as Not Found.
3. Press the soft button labeled Find to begin the identification process.
Find a Sensor
OK
Find Sensor C8.1/2
Ensure that the NET ID has
been set to
C8, and that the
NET and PWR LEDs are lit.
SelectOK
NOTE: This process merely serves as a guide to ensure that the Net IDs of
GLS-SIM modules and DIN-IO8 modules are set correctly. There is no
actual identification function.
4. Set the Net ID of the DIN-IO8 or GLS-SIM to the value shown on the IPAC
display.
Use the front panel to set the Net ID on the DIN-IO8.
DIN-IO8 Net ID Setting for Net ID D4
For detailed instructions on setting a DIN-IO8’s Net ID, refer to the
latest version of the DIN-IO8 DIN Rail Versiport Module Operations &
Installation Guide (Doc. 6664) which is available for download from
the Crestron website.
Setup Guide – DOC. 6660B Integrated Professional Automation Computer: IPAC-GL1 41