Setup guide

Integrated Professional Automation Computer Crestron IPAC-GL1
Disable/Enable Timeclock (IPAC function buttons only) – Toggles
the timeclock on and off.
Lock (IPAC function buttons only) – Locks front panel keypad.
Unlock (IPAC function buttons only) – Unlocks front panel keypad.
Lock/Unlock (IPAC function buttons only) – Toggles between front
panel keypad unlocked/locked.
6. If a button is set to On, Off, Toggle, or Custom, the loads that will be
affected by the button press must be selected.
Select Loads
Set All Clr All OK
L1.1 = Off
L1.2 = ---
L1.3 = Off
L1.4 = ---
Select
Loads
B0.1
SelectAdjust
a. A list of loads will be displayed. Each load is assigned a Load ID. For
example:
Load L1.1 represents circuit number 1 in panel 1.
Load L3.16 represents circuit number 16 in panel 3.
Affected loads will have the function listed next to their Load ID.
Loads that will not be affected will have --- next to their Load ID.
Select Loads
Set All Clr All OK
L1.1 = Toggle
L1.2 = ---
L1.3 = Toggle
L1.4 = ---
Select
Loads
B0.1
SelectAdjust
b. To select a load to be controlled, turn the selection knob to the desired
load and press the ENTER button. The controlled function will be
displayed. To deselect a load (to make it unaffected by the button
press), press the ENTER button again. The load will be listed with ---.
22 Integrated Professional Automation Computer: IPAC-GL1 Setup Guide – DOC. 6660B