Setup: Panels (Continued)
Panels: Set External Loads’ IDs
Each load in an external panel is controlled by a lighting module installed
in the external panel. To properly control the external loads in a system,
the connected modules must be identified to the GL-IPAC-SW8.
Set the ID of an external module according to the list on the right side of
the screen. Press OK to exit the screen.
NOTE: ERR indicates that a module ID cannot be found.
Internally Connected Occupancy Sensors
Occupancy Sensors: “Internal Sensor Test” Screen
From the “Occ Sensr List” screen highlight an internal sensor using the
up and down arrows and press Test to enter the “Internal Sensor Test”
screen.
Press Type to define one of the available states:
Active Hi” (Default)
Active Lo”
Normally Open (N/O)”
Normally Closed (N/C)”
Status shows the current sensor state (Active or Inactive) based on the chosen type.
Press OK to save the setting and return to the “Occ Sensor List” screen.
Cresent Connected Occupancy Sensors
Occupancy Sensors: “Find Sensor B1.1” Screen
NOTE: Internal sensors, wired directlly to the GL-IPAC-SW8, do not
need to be discovered.
External Cresnet sensors range from B0.1 through B9.1. Highlight the
external sensor from the “Occ Sensr List” screen and then press Find
to set IDs for Cresnet occupancy sensors. Three options to find the
sensors are presented:
Set ID using IR Remote allows sensor to be found using an IR
remote. This requires a direct view of the sensor, but does not
require physical access to the sensor.
Find by pressing test button allows sensor to be found by pressing the button on the inside of the sensor. This requires the
sensor to be physically accessible, which may require a ladder or step stool.
Find by serial number allows the sensor to be found by entering the serial number of the sensor. The sensors serial number
must be recorded prior to installation.
Use the up and down arrows to select the desired option and press OK.
Occupancy Sensors: “Sensor B1 Test” Screen
After a Cresnet occupancy sensor is found, press Test to confirm
functionality.
State describes the current state of the sensor: occupied or vacant.
Raw shows what the sensor is currently detecting; every time
movement is sensed the radio button fills in.
Timeout is the time the sensor must detect continuous vacancy
before going to its vacant state. Timeout can be local, 30 seconds,
2 minutes, 5 minutes, 10 minutes, 15 minutes, or 30 minutes. The
local setting uses the timeout set via the IR remote. Any
programming overrides the occupancy sensors setings.
Press TmOut to change the time before the occupancy sensor times out.
Press OK to save settings.
Occupancy Sensors: “Occ Sensr List” Screen
To configure occupancy sensors for the GL-IPAC-SW8, select
Occupancy Sensors from the “Setup” menu. The “Occ Sensr List”
screen provides a list of all connected occupancy sensors. There can be
a total of 24 occupancy sensors connected to the GL-IPAC-SW8. There
are three types of occupancy sensors:
4 internal, non-system sensors (Sensor 1 to 4)
10 external Cresnet sensors (Sensors B0.1 to B9.1)
10 external, non-system sensors - Connected to Cresnet via
GLS-SIM (Sensors C0.1 to C9.1)
Press Exit to save the settings and return to the “Setup” menu.
OK
OK
OK
ERR
---
Set Module ID’s
in PNL-1 to these
values:
11
12
13
14
SelectOK
Test
Sensor 1
Sensor 2
Sensor 3
Sensor 4
Occ
Sensr
List
Loads Exit
TmOut OK
Sensor B1 Test
B1.1: State = Vacant
B1.1: Raw O
B1.1: Timeout - 30s
OK
Find Sensor B1.1
Set ID using IR Remote
Find by pressing test button
Find by serial number
OKType
Internal Sensor Test
IN 1: Type=Active Hi
Status=Inactve
GLS-SIM Connected Occupancy Sensors
Occupancy Sensors: “Find Sensor C0.1” Screen
External occupancy sensors connected to a GLS-SIM range from
C0.1 through C9.1. Highlight the external sensor from the “Occ
Sensr List” screen and then press Find. Set the ID on the GLS-SIM
to match the settings displayed on the GL-IPAC-SW8.
Press OK to return to the “Occ Sensr List” screen.
OK
Find Sensor C0.1
Ensure that the NET ID has
been set to CO, and that the
NET and PWR LEDs are lit.
Occupancy Sensors
(Continued on following page)