Installation guide

Power Switching Cabinet GLPX-SW-FT Crestron Green Light Express
®
16 Crestron Green Light Express
®
Power Switching Cabinet GLPX-SW-FT Installation Guide DOC. 6886B
Control Wiring (Section B)
The bottom of the cabinet contains Cresnet
®
connections for interfacing to the rest of the Crestron
®
control system.
It also provides override input which can be tied to devices such as the GLS-PLS-120/277 phase-loss sensor, or
other devices that provide a dry contact closure (manual switch, fire alarm relay, etc.).
To ensure optimum performance over the full range of your installation topology, use Crestron certified wire.
Failure to do so may incur additional charges if support is required to identify performance deficiencies because of
using improper wire.
NOTE: Interface connectors for NET and OVR ports are provided.
Wire Gauge and Torque Values
TERMINAL CONNECTOR MAX
WIRE RANGE
TORQUE STRIP
LENGTH
NET
26-12 AWG 4.43 lb-in (0.5 Nm) 1/4” (6 mm)
OVR
26-12 AWG 4.43 lb-in (0.5 Nm) 1/4” (6 mm)
Connector Wiring
NOTE: For instructions on network wiring, refer to “Appendix B: Network Wiring” on page 21
.