Installation guide

Power Switching Cabinet GLPS-HDSW-FT CRESTRON GREEN LIGHT
®
EXPRESS
Feed-Through and Load Wiring (Section A)
NOTE: Use copper conductors only – rated 75°C.
Wire Gauge and Torque Values
TERMINAL CONNECTOR MAX
WIRE RANGE
TORQUE STRIP
LENGTH
INPUT 26-10 AWG 5.31 lb-in (0.6 Nm) to
7.08 lb-in (0.8 Nm) max
3/8”
(9 mm)
OUTPUT/CONTACT 26-10 AWG 5.31 lb-in (0.6 Nm) to
7.08 lb-in (0.8 Nm) max
3/8”
(9 mm)
GROUND LUG 14-4 AWG 25-45 lb-in
(2.8-5.1 Nm)
3/4"
(19 mm)
Load Wiring for GLXX -HDSW8 and GLXX- HDSW16
SERVICE
SCREWDRIVER
LINE 1*
TO LOAD
LINE 2*
TO LOAD
L
SINGLE-POLE
DOUBLE-POLE
LINE
TO LOAD
* Lines 1 and 2 must be on different phases.
NOTE: All GLXX-HDSW8 or GLXX-HDSW16 modules must be connected together in series to the
GLXX-CNTRL Express Controller using the quick-connect jumper wires provided.
8 GREEN LIGHT
®
EXPRESS Power Switching Cabinet GLPS-HDSW-FT Installation Guide – DOC. 6887A