Installation guide

Power Switching Cabinet GLPS-HDSW-FT CRESTRON GREEN LIGHT
®
EXPRESS
Crestron Network to Mini Network Interconnect Diagram
24
Y
Z
G
To Mini Network Device
Front
View
Front
View
To Network Device
24
Y
Z
G
Black
Blue
White
Red
Shield*
Red
White
Blue
Black
Wire Nuts &
Jumper Wires
CAUTION: Possible Equipment Damage if Miswired
Pair A
22 AWG Twisted
Blue = Z
White = Y
Pair B
18 AWG Parallel
Black = Ground
Red = 24 VDC
Do not power up system until all wiring is verified. Care should
be taken to ensure Data (Y & Z), and Power (24 & G)
connections are not crossed.
Ground Shield at the Control System end only.
Model CNTBLOCK network terminal expander and diagnostic
tool for the Cresnet system is recommended for testing purposes
and wiring convenience.
Jumper wires: Use #18 AWG. Use a wire nut that accomodates
all three wires.
To Control System
G
Z
Y
24
Front
View
Black
Green
Green
restron recommends the use of C2N-HBLOCK or CNTBLOCK as the
preferred method to daisy chain or expand the Cresnet network. If the blocks
are not available, use the method as shown.
NOTE: C
20 GREEN LIGHT
®
EXPRESS Power Switching Cabinet GLPS-HDSW-FT Installation Guide – DOC. 6887A