Installation guide

CRESTRON GREEN LIGHT
®
EXPRESS Power Switching Cabinet GLPS-HDSW-FT
Crestron Network Interconnect Diagram
CAUTION: Possible Equipment Damage if Miswired
To Control System
G
Z
Y
24
Front
View
To Network Device
24
Y
Z
G
Front
View
To Network Device
24
Y
Z
G
Front
View
Pair A
22 AWG Twisted
Blue = Z
White = Y
Pair B
18
AWG Parallel
Black = Ground
Red = 24 VDC
Shield
Do not power up system until all wiring is verified. Care should
be taken to ensure Data (Y & Z), and Power (24 & G)
connections are not crossed.
Ground Shield at the Control System end only.
Model CNTBLOCK network terminal expander and diagnostic
tool for the Cresnet system is recommended for testing purposes
and wiring convenience.
Crestron recommends the use of C2N-HBLOCK or CNTBLOCK as the
preferred method to daisy chain or expand the Cresnet network. If the blocks
are not available, use the method as shown.
NOTE:
Green
Green
Green
Installation Guide – DOC. 6887A GREEN LIGHT
®