Installation guide

Power Switching Cabinet GLPS-HDSW-FT CRESTRON GREEN LIGHT
®
EXPRESS
Testing
Manual Control
Lighting loads can be manually controlled from the front panel.
TOGGLES LOCAL
CONTROL ON/OFF
TOGGLES SELECTED
RELAY ON/OFF
USE UP/DOWN ARROWS
TO SELECT RELAY TO
CONTROL
(NET ID WILL DISPLAY
RELAY NUMBER)
RED LED ILLUMINATES
WHEN LOCAL
CONTROL IS ENABLED
NOTE: To disable local control, press the ENABLE button again or wait for two minutes. The red LED beside the
button will deactivate.
NOTE: The control system program may change the settings if the Override mode is not enabled.
Override Mode
The Override mode overrides the control system program and sets all of the output states to the stored override
values. For instructions on saving override settings, refer to “Save Override Settings” below.
To enable Override mode, press and release the OVR button. The OVR LED flashes slowly.
NOTE: If the Override mode was enabled from an external device (i.e. a contact closure is present on the
OVERRIDE terminals), the OVR LED will flash quickly. Pressing the OVR button has no effect.
To disable Override mode, press the OVR button again. The OVR LED extinguishes and the outputs return to the
states set by the control system program.
NOTE: If override states have not been stored, the factory default override state is all loads on.
Save Override Settings
The state of each output can be saved as an override setting, which can be automatically recalled when the Override
mode is enabled.
NOTE: The control system program has a setting that can prevent locally saving the override state. If this setting is
enabled, the display shows “Er” when trying to save override states. For more information, refer to the SIMPL
Windows help file.
To save the states of all outputs as the override setting, press and hold the OVR button for three seconds until the
OVR LED blinks once.
System Operation and Commissioning
This cabinet has been designed as a component of a programmed Crestron system. System commissioning by an
authorized Crestron representative
must be performed to ensure system operation.
Once the cabinet has been wired and the modules have been tested, contact Crestron at 1-888-CRESTRON
[1-888-273-7876] to schedule commissioning.
14 GREEN LIGHT
®
EXPRESS Power Switching Cabinet GLPS-HDSW-FT Installation Guide – DOC. 6887A