Installation guide

Crestron DIN-AO8 DIN Rail Analog Output Module
Operation
Net ID
Use the NET ID buttons to change the Net ID of the DIN-AO8. For more
information on Net ID, refer to “Identity Code” on page 10.
Manual
Control
The level of each of the analog outputs can be manually controlled from
the front panel.
To toggle the output between off (0V) and the programmed upper limit
(10V), tap an output button. The corresponding LED illuminates and the
output level is shown on the NET ID display (“oF” for off, “On” for on)
for two seconds after the button is released.
To ramp the voltage up or down (until it reaches a limit), press and hold
the output button. To change the ramp direction, release the output
button, then press and hold it again. The corresponding LED illuminates
and the output level is shown on the NET ID display as a percentage (01-
99) for two seconds after the button is released.
NOTE: The control system program may change the settings if the
Override mode is not enabled.
Override
Mode
The Override mode overrides the control system program and sets all of
the output levels to the saved override values. For instructions on saving
override levels, refer to “Save Override Levels” on page 22.
To enable the Override mode, press and release the OVR button. The
OVR LED flashes slowly.
NOTE: If the Override mode was enabled from an external device (i.e.
a contact closure is present on the OVERRIDE terminals), the OVR
LED flashes quickly. Pressing the OVR button has no effect.
To disable the Override mode, press the OVR button again. The OVR
LED extinguishes and the output levels return to the values set by the
control system program.
NOTE: If override levels have not been saved, the factory default
override level is 100%.
Operations & Installation Guide – DOC. 6663A DIN Rail Analog Output Module: DIN-AO8 21