Installation guide
DIN Rail Versiport Module Crestron DIN-IO8
Cable Length Equation
L = Length of run (or chain) in feet
R = 6 Ohms (Crestron Certified Wire : 0.75 MM (18 AWG))
P = Cresnet power usage of entire run (or chain )
2
L <
40,000
R x P
Where:
Make sure the cable length value is less than the value calculated on the
right side of the equation. For example, a Cresnet run using 0.75mm
2
(18 AWG) Crestron Certified Wire and drawing 20 watts should not have
a length of run more than 101 meters (333 feet). Cresnet-HP cannot be
used.
NOTE: All Crestron certified Cresnet wiring must consist of two
twisted pairs. One twisted pair is the +24V conductor and the GND
conductor and the other twisted pair is the Y conductor and the Z
conductor.
Strip and Tin
Wire
When daisy-chaining Cresnet units, strip the ends of the wires carefully
to avoid nicking the conductors. Twist together the ends of the wires that
share a pin on the network connector and tin the twisted connection.
Apply solder only to the ends of the twisted wires. Avoid tinning too far
up the wires or the end becomes brittle. Insert the tinned connection into
the Cresnet connector and tighten the retaining screw. Repeat the
procedure for the other three conductors.
Add Hubs
Use of a Cresnet Hub/Repeater (DIN-HUB) is advised whenever the
number of Cresnet devices on a network exceeds 20 or when the
combined total length of Cresnet cable exceeds 914 meters (3000 feet).
Reference Documents
The latest version of all documents mentioned within the guide can be
obtained from the Crestron website (
www.crestron.com/manuals). This
link will provide a list of product manuals arranged in alphabetical order
by model number.
List of Related Reference Documents
DOCUMENT TITLE
2-Series Control Systems Reference Guide
26 • DIN Rail Versiport Module: DIN-IO8 Operations & Installation Guide – DOC. 6664A