Installation guide

DIN Rail Versiport Module Crestron DIN-IO8
Setup
Network Wiring
When wiring the Cresnet network, consider the following:
Use Crestron Certified Wire.
NOTE: Cresnet-HP wire cannot be used.
Use Crestron power supplies for Crestron equipment.
Provide sufficient power to the system.
CAUTION: Insufficient power can lead to unpredictable results
or damage to the equipment. Please use the Crestron Power
Calculator to help calculate how much power is needed for the
system (
www.crestron.com/calculators).
Use of a Cresnet hub/repeater (DIN-HUB) is advised whenever the
number of Cresnet devices on a network exceeds 20, or when the
combined total length of Cresnet cable exceeds 914 meters (3000
feet).
For more details, refer to “
Check Network Wiring” on page 25.
Identity Code
The Net ID of the DIN-IO8 has been factory set to 84. The Net IDs of
multiple DIN-IO8 devices in the same system must be unique. Net IDs
are changed on the front panel of the DIN-IO8 or from a personal
computer (PC) via Crestron Toolbox™ (refer to “
Establishing
Communication
” on page 21).
To set the Net ID using the front panel:
Press the SETUP button to enter the Setup mode. The SETUP
LED illuminates.
Press the left button under the NET ID display to change the most
significant digit of the Net ID or press the right button under the
NET ID display to change the least significant digit of the Net ID
number.
10 DIN Rail Versiport Module: DIN-IO8 Operations & Installation Guide – DOC. 6664A