Crestron DIN-AP3 DIN Rail 3-Series™ Automation Processor Operations & Installation Guide
Regulatory Compliance As of the date of manufacture, the DIN-AP3 has been tested and found to comply with specifications for CE marking and standards per EMC and Radiocommunications Compliance Labelling. Federal Communications Commission (FCC) Compliance Statement CAUTION: Changes or modifications not expressly approved by the manufacturer responsible for compliance could void the user’s authority to operate the equipment.
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor Contents DIN Rail 3-Series Automation Processor: DIN-AP3 1 Introduction ............................................................................................................................... 1 Features and Functions ................................................................................................ 1 3-Series Engine............................................................................................................
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor DIN Rail 3-Series Automation Processor: DIN-AP3 Introduction The DIN-AP3 is a 3-Series™ control processor designed for lighting and automation applications. DIN rail mounting enables modular installation alongside Crestron® DIN Rail lighting and automation control modules and other third-party DIN rail mountable devices.
DIN Rail 3-Series Automation Processor Crestron DIN-AP3 3-Series Engine Today’s commercial buildings and custom homes comprise more technology than ever before, and all these systems need to be networked, managed, and controlled in fundamentally new ways. The IP-based 3-Series engine platform is engineered from the ground up to deliver a network-grade server appliance capable of faithfully handling everything from boardroom AV and home theater control to total building management.
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor Cresnet Cresnet is the communications backbone for Crestron lighting modules, wall box dimmers, shade controllers, thermostats, keypads, touch screens, and many other devices. This flexible 4-wire bus streamlines the wiring of a complete Crestron system. The DIN-AP3 includes a pair of Cresnet master ports (paralleled) capable of supporting approximately 20 typical devices.
DIN Rail 3-Series Automation Processor Crestron DIN-AP3 BACnet/IP Native support for the BACnet/IP communication protocol provides a direct interface to third-party building management systems over Ethernet, simplifying integration with HVAC, security, fire and life safety, voice and data, lighting, shades, and other systems. Using BACnet/IP, each system runs independently with the ability to communicate together on one platform for a truly smart building*. * License required.
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor DIN-AP3 Specifications (Continued) SPECIFICATION Ethernet Power Cresnet Power Usage Default Net ID Environmental Installation Location Temperature Humidity Heat Dissipation Enclosure DETAILS 10/100 Mbps; auto-switching, auto-negotiating, auto-discovery, full/half duplex, industry-standard TCP/IP stack, UDP/IP, CIP, DHCP, SSL, IEEE 802.1X; SNMP; BACnet/IP1; IPv4 or IPv6, Active Directory authentication, IIS v.6.
DIN Rail 3-Series Automation Processor Crestron DIN-AP3 DIN-AP3 Specifications (Continued) SPECIFICATION Dimensions Height Width Depth Weight Available Accessories: 3-Series BACnet/IP Support DIN-1DIMU4 DIN-2MC2 DIN-4DIMFLV4 DIN-8SW8 DIN-AO8 DIN-BLOCK DIN-HUB DIN-IO8 DIN-PWS50 DETAILS 3.72 in (95 mm) 6.28 in (160 mm) 2.
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor Physical Description This section provides information on the connections, controls, and indicators available on the DIN-AP3. DIN-AP3 Physical View Operations & Installation Guide – DOC.
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor DIN-AP3 Overall Dimensions – Front View 1 2 3 4 6 5 3.56 in (91 mm) 3.72 in (95 mm) LAN 7 8 9 10 11 DIN-AP3 Overall Dimensions – Bottom View 6.28 in (160 mm) 2.29 in (59 mm) 12 8 • Automation Processor: DIN-AP3 Operations & Installation Guide – DOC.
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor DIN-AP3 Physical Drawing – Top View 13 DIN-AP3 Physical Drawing – Side View Operations & Installation Guide – DOC.
DIN Rail 3-Series Automation Processor Crestron DIN-AP3 Connectors, Controls & Indicators # CONNECTORS*, CONTROLS & INDICATORS DESCRIPTION 1 IO G, 8-1 2 PWR LED 3 NET LED 4 HW-R Button (1) (1) 9-pin 3.5 mm detachable terminal block comprising (8) “Versiport” digital input/output or analog input ports (referenced to GND); Digital input: Rated for 0-24 volts dc, input impedance 20 kΩ, logic threshold >3.125 V low/0 and <1.
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor Connectors, Controls, and Indicators (Continued) # CONNECTORS*, CONTROLS, AND INDICATORS DESCRIPTION 5 SW-R Button (1) Recessed miniature push button for software reset (restarts the SIMPL program) 6 Relays 1-4 7 NET – 24 Y Z G 8 MSG LED (1) 8-pin 3.5 mm detachable terminal blocks comprising (4) normally open, isolated relays; Rated 1 amp, 30 volts ac/dc; MOV arc suppression across contacts (2) 4-pin 3.
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor Connectors, Controls, and Indicators (Continued) # CONNECTORS*, CONTROLS, AND INDICATORS 9 COM 1-2 DESCRIPTION (2) 5-pin 3.5 mm detachable terminal block; Bidirectional RS-232/422/485 port; Up to 115.2 kBb; Hardware and software handshaking support RS-232 GND TX RX RTS CTS RS-422 GND TXRX+ TX+ RX- RS-485 GND* TX-/RXNot Used TX+/RX+ Not Used * A ground terminal connection is recommended but not required.
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor Connectors, Controls, and Indicators (Continued) # CONNECTORS*, CONTROLS, AND INDICATORS 11 COMPUTER Pin 2 Pin 1 Pin 3 Pin 4 12 LAN Pin 1 Pin 8 Green LED Amber LED DESCRIPTION (1) USB Type B female, USB 1.
DIN Rail 3-Series Automation Processor Crestron DIN-AP3 Setup Network Wiring When wiring the Cresnet/Ethernet network, consider the following: • Use Crestron Certified Wire. • Use Crestron power supplies for Crestron equipment. • Provide sufficient power to the system. CAUTION: Insufficient power can lead to unpredictable results or damage to the equipment. Use the Crestron Power Calculator to help calculate how much power is needed for the system (www.crestron.com/calculators).
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor To prevent overheating, do not operate this product in an area that exceeds the environmental temperature range listed in the table of specifications. Consider using forced air ventilation to reduce overheating. Consideration must be given if installed in a closed or multiunit rack assembly since the operating ambient temperature of the environment may be greater than the room ambient temperature.
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor Hardware Connections for the DIN-AP3 – Front View I/O (G, 8 - 1): To Controllable Devices From Device Outputs -Contact Closures -Relay Closures COM (1 - 2): To RS-232/422/485 Devices NET (24 Y Z G): To Any Cresnet Network Device 16 • Automation Processor: DIN-AP3 RELAY (1 - 8): To Controllable Devices IR/SERIAL (1 - 4): To IRP2 or Serial Devices COMPUTER: To Computer Console Operations & Installation Guide – DOC.
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor Hardware Connections for the DIN-AP3 – Bottom View LAN: 10BASE-T / 100BASE-TX Ethernet to LAN Hardware Connections for the DIN-AP3 – Top View MEMORY: For SD Card NOTE: Ensure the unit is properly grounded by connecting the chassis ground lug to an earth ground (building steel). NOTE: To prevent overheating, do not operate this product in an area that exceeds the environmental temperature range listed in the table of specifications.
DIN Rail 3-Series Automation Processor Crestron DIN-AP3 Uploading and Upgrading Crestron recommends using the latest programming software and that each device contains the latest firmware to take advantage of the most recently released features. However, before attempting to upload or upgrade it is necessary to establish communication. Once communication has been established, files (for example, programs or firmware) can be transferred to the control system (or device).
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor 3. For Connection Type, select USB. When multiple USB devices are connected, identify the DIN-AP3 by entering “DIN-AP3” in the Model text box, the unit’s serial number in the Serial text box or the unit’s hostname (if known) in the Hostname text box. 4. Click OK. Communications are confirmed when the device information is displayed. TCP/IP Ethernet Communication DIN-AP3 N LA PC Running Crestron Toolbox The DIN-AP3 connects to PC via Ethernet: 1.
DIN Rail 3-Series Automation Processor Crestron DIN-AP3 Upgrade DIN-AP3 firmware via Crestron Toolbox. 1. Establish communication with the DIN-AP3 and display the “System Info” window. 2. Select Functions | Firmware… to upgrade the DIN-AP3 firmware. 20 • Automation Processor: DIN-AP3 Operations & Installation Guide – DOC.
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor Configure for Operations Before setting up the DIN-AP3 the time and time zone need to be set. The DIN-AP3 can also be further configured using a Web browser. Set Date and Time 1. Establish communication with the DIN-AP3 as described in “Establishing Communication” on page 18. 2. In Crestron Toolbox, select Functions | System Clock…. 3. Set the date and time. Online Configuration The DIN-AP3 can be configured using the built-in Web-based setup tool.
DIN Rail 3-Series Automation Processor Crestron DIN-AP3 Splash Screen 2. Click Setup to display the “DIN-AP3 Setup” menu. “DIN-AP3 Setup” Menu The “DIN-AP3 Setup” menu displays the IP address, hostname and MAC address of the device. It also allows access to various setup and programming screens. The “DIN-AP3 Setup” menu contains buttons for Ethernet Setup, Application Setup, Input/Output Control, Diagnostics, and About, as shown in the illustration above.
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor 3. Click one of the following options: • Ethernet Setup – Configures the DIN-AP3’s Ethernet settings and displays DHCP, hostname, IP address, subnet mask, default router, domain, and MAC address settings. ⇒ Click Advanced Settings to specify DNS servers, Web server settings, and SSL settings. ⇒ Click MyCrestron Dynamic DNS to configure the myCrestron.com Dynamic DNS service. ⇒ Click Ethernet Diagnostics to test Ethernet communications.
DIN Rail 3-Series Automation Processor Crestron DIN-AP3 Problem Solving Troubleshooting The following table provides corrective action for possible trouble situations. If further assistance is required, please contact a Crestron customer service representative. DIN-AP3 Troubleshooting TROUBLE POSSIBLE CAUSE(S) CORRECTIVE ACTION Device does not function. Device is not communicating with the network. Use Crestron Toolbox to poll the network. Verify network connection to the device.
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor DIN-AP3 Troubleshooting (Continued) TROUBLE POSSIBLE CAUSE(S) Compilation error RLCMCVT166 and RLCMCVT177. System locks up. Poor analog versus serial signal definition in the SIMPL Windows program. Various. Cresnet device does not respond. Device not wired correctly. Improper NET ID used. Loss of functionality due to electrostatic discharge. Improper grounding. CORRECTIVE ACTION Confirm properly defined signal definition in the program.
DIN Rail 3-Series Automation Processor Crestron DIN-AP3 DIN-AP3 Troubleshooting (Continued) TROUBLE POSSIBLE CAUSE(S) CORRECTIVE ACTION A/V system device does not respond. IRP2 or serial port not placed properly. Verify placement of IRP2 (hold phosphor card under IRP2 while pressing button) and tighten serial cables. Verify that proper IR or serial port is defined. Verify that serial cable is wired correctly for RS-232, 422, 485.
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor must be taken into consideration. Use Crestron Certified Wire only. If Cresnet units are to be daisy chained on the run, the Cresnet power usage of each network unit to be daisy chained must be added together to determine the Cresnet power usage of the entire chain. If the unit is run from a Crestron system power supply network port, the Cresnet power usage of that unit is the Cresnet power usage of the entire run.
DIN Rail 3-Series Automation Processor Crestron DIN-AP3 Reference Documents All documents mentioned in this guide are available from the Crestron Web site.
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor Return and Warranty Policies Merchandise Returns / Repair Service 1. No merchandise may be returned for credit, exchange or service without prior authorization from Crestron. To obtain warranty service for Crestron products, contact an authorized Crestron dealer. Only authorized Crestron dealers may contact the factory and request an RMA (Return Merchandise Authorization) number.
DIN Rail 3-Series Automation Processor Crestron DIN-AP3 This page is intentionally left blank. 30 • Automation Processor: DIN-AP3 Operations & Installation Guide – DOC.
Crestron DIN-AP3 DIN Rail 3-Series Automation Processor This page is intentionally left blank. Operations & Installation Guide – DOC.
Crestron Electronics, Inc. 15 Volvo Drive Rockleigh, NJ 07647 Tel: 888.CRESTRON Fax: 201.767.7576 www.crestron.com Operations & Installation Guide – DOC. 7491A (2035917) 07.13 Specifications subject to change without notice.