Specifications

Wireless
RF Transceiver: 2-way RF, 2.4 GHz ISM Channels 11-26 (2400 to
2483. 6 MHz), IEEE 802.15.4 compliant
Range (typical): 150' indoor, 250' outdoor; Subject to site-
specific conditions
RF Transmit Power: 10mW
Gateway: Requires a P-MNETGW Gateway/Transceiver
Connections
HVAC: (2) 4-position terminal blocks comprising the following:
RH: Reference Heat – Used for calls to heating system;
RC: Reference Cool – Used for calls to cooling system;
G: Fan Energized to RC during call for fan;
Y: Compressor – Energized to RC when compressor is run;
C: 24V AC common terminal supplies remote power to thermostat;
W: Heat – Energized to RH during a call for heat in heat/cool systems
or aux heat in heat pump systems;
O: Changeover control – Energized to RC during cooling modes;
B: Energized to RC during heating modes
Buttons
Mode: Cycles through available System Modes: OFF, HEAT, AUX HEAT ONLY
(for heatpump or dual-fuel systems only) and COOL
Fan: Toggles fan setting between FAN AUTO and FAN ON
Raise: Raises the setpoint
Lower: Lowers the setpoint
Hold (combination): Pressing MODE and FAN buttons simultaneously
enters/exits HOLD mode
Setup (combination): Holding the FAN button, then pressing the RAISE and
LOWER buttons simultaneously for 5 seconds enters SETUP mode; pressing
mode button advances to next setup parameter/function; pressing RAISE or
LOWER adjusts value of current setup parameter or executes
current setup function, pressing FAN button exits SETUP mode
Display
Type: Backlit LCD with (2) large 7-segment digits, (2) small 7-segment
digits, (14) dedicated symbols; Displays ambient temperature, setpoint,
system mode, fan setting, call activity, low battery, RF or control system
communication errors, firmware download progress, setup parameter/
function and value
Measurement Range
Ambient Temperature: -10° to 110°F (-23° to 43°C)
Display Limits: -9° to 99°F (-9° to 43°C)
Setpoint Range
Heat Setpoint: 38° to 89°F (3° to 32°C)
Cool Setpoint: 59° to 99°F (15° to 37°C), or 38° to 99°F (3° to 37°C)
extended cool mode enabled
Relay Rating
1 Amp @ 40 Volts DC or 24 Volts AC (nominal)
Environmental
Temperature: -10° to 110°F (-23° to 43°C)
Humidity: 10% to 90% RH (non-condensing)
Power Requirements
24V: 0.24 Watts (10 mA) @ 24 Volts AC, supplied by heating or
cooling system
Battery: (2) AA batteries required, estimated 1 year normal operation
Housing
Injection-molded plastic, surface-mountable to the front of a horizontally-
oriented 1-gang electrical box
Dimensions
Height: 4.50 in (11.43 cm)
Width: 5.53 in (14.05 cm)
Depth: 1.03 in (2.60 cm)
Weight
6.7 oz (0.19 kg)
* Heat pump systems require addition of an outdoor temperature sensor;
contact your Crestron representative for additional design assistance.