Specifications

SPECIFICATIONS
!
19
crestron.eu/prodigy
Load Ratings
Switch Channels: 4
Maximum Per Channel: 5 Amps @ 120 to 240 Volts AC, 50/60 Hz;
600 Watts @ 120 Volts AC; 1150 Watts @ 230 Volts AC; 1200 Watts @
240 Volts AC
Module Total: 10 Amps @ 120 to 240 Volts AC, 50/60 Hz;1200 Watts @
120 Volts AC; 2300 Watts @ 230 Volts AC; 2400 Watts @ 240 Volts AC
Load Types: Forward Phase (leading edge), Incandescent, Neon/Cold
Cathode, Magnetic Low Voltage, Dimmable 2 Wire Fluorescent
Input Voltage
Line Power120 to 240 Volts AC, 50/60 Hz
Power Requirements
Cresnet Power Usage 0.6 Watts (0.03 Amps @ 24 Volts DC) when line
power is not available
Controls & Indicators
NET ID:
(2) 7-Segment green LED digits and (2) miniature pushbuttons
for setting Cresnet ID; digits also display output levels and protection/error
codes
SETUP:
(1) Red LED and (1) recessed miniature pushbutton for enabling
setup mode and touch-settable ID
OVR
: (1) Red LED and (1) miniature pushbutton for enabling override mode
and saving override presets
PWR
: (1) Green LED, normally indicates AC line power is connected to either
LIVE terminal, blinks when only powered by Cresnet
NET
: (1) Yellow LED, indicates communication with the control processor
RESET
: (1) Recessed miniature pushbutton, resets internal processor
FWD 1 – 4:
(4) Red LEDs, illuminate when a corresponding channel is
operating in forward-phase mode
REV 1 – 4
: (4) Red LEDs, illuminate when a corresponding channel is
operating in reverse-phase mode
NON-DIM 1 – 4:
(4) Red LEDs, illuminate when a corresponding channel is
operating in non-dim mode
Channel Mode Select 14:
(4) Recessed miniature pushbuttons, used to
select each channel’s operating mode
LOADS 14:
(4) Red LEDs and (4) miniature pushbuttons for status
indication and local control of each channel
Connectors
NET
: (2) 4-pin 3.5mm detachable terminal blocks, paralleled;
Cresnet slave port
OVERRIDE
: (2) 2-pin 3.5mm detachable terminal blocks, paralleled; Sensing
input for external low-voltage contact closure;
Activates override mode when
a closure is present; Minimum Closure Rating: 10mA (per module) at 24
Volts
LIVE
: (2) Captive screw terminals†, brown; Line power input
NEUTRAL
: (5) Captive screw terminals†, blue
DIMMED LIVE 1 – 4
: (4) Captive screw terminals†, red; Dimmer channel
outputs 1 - 4
Ground:
(5) Captive screw terminals†, green
Environmental
Temperature: 32° to 104°F (0° to 40°C)
Humidity: 10% to 90% RH (non-condensing)
Heat Dissipation: 60 BTU/hr @240 Volts with 2 channels at 5 Amps;
50 BTU/hr @ 120 Volts with 2 channels at 5 Amp
Enclosure
Aluminum with polycarbonate label overlay, 35mm DIN EN 60715 rail
mount, DIN 43880 form factor for enclosures with 45mm front panel cutout,
occupies 12 DIN module spaces (216mm)*
Dimensions
Height: 3.71 in (9.42 cm)
Width: 8.49 in (21.55 cm)
Depth: 2.35 in (5.95 cm)
Weight
2.1 lb (912 g)
Required
DIN-PWS50
: DIN Rail 50 Watt Cresnet Power Supply (**)
- 50 Watt Cresnet power supply module
- Powers Cresnet devices
- Includes 3 Cresnet power ports
(*) Unit dissipates significant heat when fully loaded and should be mounted
in an enclosure that is sufficiently ventilated to maintain an ambient
temperature not exceeding 104°F (40°C). Maintain 4 inches (10 cm)
minimum spacing above and below for proper ventilation and heat
dissipation, 6 inches (15 cm) spacing recommended.
(**) Only one DIN-PWS50 per Prodigy System required