Installation guide

DIN Rail High-Voltage Switch Crestron DIN-8SW8-I
Override
Mode
The Override mode overrides the control system program and sets all of
the output states to the stored override values. For instructions on saving
override settings, refer to “Save Override Settings” on page 24.
To enable Override mode, press and release the OVR button. The OVR
LED flashes slowly.
NOTE: If the Override mode was enabled from an external device (i.e.
a contact closure is present on the OVERRIDE terminals), the OVR
LED will flash quickly. Pressing the OVR button has no effect.
To disable Override mode, press the OVR button again. The OVR LED
extinguishes and the outputs return to the states set by the control system
program.
NOTE: If override states have not been stored, the factory default
override state is all loads on.
Save
Override
Settings
The state of each output can be saved as an override setting, which can be
automatically recalled when the Override mode is enabled.
NOTE: The control system program has a setting that can prevent
locally saving the override state. If this setting is enabled, the display
shows “Er” when trying to save override states. For more information,
refer to the SIMPL Windows help file.
To save the state of an output as an override setting, press and hold the
OVR button for three seconds. The OVR LED blinks to indicate the new
override setting has been stored.
Reset
To reboot the DIN-8SW8-I, press the RESET button. The outputs will
be set to the states currently specified by the control system program. If
the control system does not provide any values, the outputs will be set to
the previously set values.
24 DIN Rail High-Voltage Switch: DIN-8SW8-I Operations & Installation Guide – DOC. 6930A