3. When the desired Net ID is displayed, press the SETUP button to
exit the Setup mode. The SETUP LED extinguishes.
NOTE: If an invalid Net ID is set (00, 02, FF), “Er” will be
displayed on the NET ID display. The DIN-8SW8-I will revert to
the previously set Net ID.
NOTE: The DIN-8SW8-I will exit the Setup mode after 10
seconds of inactivity. The DIN-8SW8-I will revert to the
previously set Net ID.
NOTE: Regardless of the method used to set the NET ID, a small
label (with numbers and letters) is provided on the front panel of
the DIN-8SW8-I to document the unit’s Net ID in the case where
power is not available. Apply a mark over the digits that
correspond to the assigned Net ID.
NET ID Label (“3C” Shown)
When setting the Net ID, consider the following:
The Net ID of each unit must match an ID code specified in the
SIMPL™ Windows program.
Each network device must have a unique Net ID.
For more details, refer to the Crestron Toolbox help file.
Installation
The DIN-8SW8-I must be installed by a licensed electrician, in
accordance with all national and local codes.
CAUTION: This equipment is for indoor use only. Mount in a well
ventilated area. The ambient temperature must be 0º to 40º C
(32º to 104º F). The relative humidity must be 10% – 90%
(non-condensing).
NOTE: When installing in an enclosure, high-voltage devices should be
grouped separately from low-voltage devices.