System information

Software Crestron D3 Pro
button has been programmed to set the level to less than the lower limit, the light will
stay at the lower limit, unless the light is instructed to go to 0%, at which point it will
turn off.
Valid values for Lower Limit range from 0% - 45%. For Upper Limit, valid values
range from 55% - 100%.
Override Level specifies the lighting level to go to when the modules are put into
override mode. An override occurs when the Override connector on the PAC2 or
CAEN-BLOCK receives a closure to ground. Valid values for override level range
from 0% to 100% for dimmable circuits; and 0% or 100% for non-dimmed circuits.
The Record check box enables the Vacation Scheduler to record light levels for a
circuit. The Vacation Scheduler is a built-in utility that memorizes and replays light
levels over a one or two week period. This is useful, as the name implies, for
maintaining a semblance of occupancy while on vacation. (The Vacation Scheduler is
only capable of learning light levels, so circuits that have non-lighting load types
such as ceiling fans cannot be learned.)
Advanced lighting properties will only be displayed for the following lighting loads:
incandescent, fluorescent 2-wire, fluorescent non-dim, magnetic low-voltage,
electronic low-voltage, neon-cold cathode, and H.I.D.
To set advanced properties for a 3-wire motor select Advanced Motor Properties
from the drop-down list at the bottom of the Load Schedule screen. Here you can set
values for Max Time, Jog Time, and Lockout Time.
Max Time sets the maximum time that the motor can remain in the Open or Close
state. That is, when an "Open" or "Close" command turns the motor on, the motor
will move in the indicated direction 1) until <Max Time> expires; 2) until another
command turns the motor off; or 3) until it hits a limit switch in the motor assembly.
Valid values for Max Time range from 10 seconds to 8 minutes. It should be set to a
value greater than the full-range travel time of the motor being controlled.
Jog Time sets the time that the motor will move in the Open or Close direction
during a "Jog" command. That is, a rising edge of a Jog Open or Jog Close command
will cause the motor to move in the indicated direction for <Jog Time> seconds.
Valid values for Jog Time range from 0.05s to 2.00s.
Lockout Time sets the minimum time that the motor must remain in the "stop" state
before changing directions between "open" and "close." If the motor is commanded
to move in one direction while it is moving in the opposite direction, the motor will
stop for Lockout Time seconds before moving in the new direction. This is done to
prevent damage to the motor, and the value should be set according to the
requirements of the particular motor being controlled.
Valid values for Lockout Time range from 0.2s to 2.00s.
30 Crestron D3 Pro Reference Guide – DOC. 5998a