Specifications

Touchpanels Crestron CT-1000 & LC-1000
24 Series 1000 Wall-Mounted Touchpanels Operations Guide – DOC. 5813B
Digital Reserved Join Numbers for Series 1000 Touchpanels
JOIN NUMBER FUNCTION
V
ALUE
1016 Standby Not Applicable
1017 Brightness Low
1018 Brightness Medium
1019 Brightness High
1020 Brightness Auto
1023 Contrast Lighten
1024 Contrast Darken
1035 Call up Setup Menu Not Applicable
1051 Cresnet ID Down
1052 Cresnet ID Up
1053 Local Mode Not Applicable
1054 Cresnet Mode Not Applicable
1084 Light Threshold Level Up
1085 Light Threshold Level Down
1086* Image Positive
1087* Image Negative
1088* Image Auto
1107 Timeout Increase
1108 Timeout Decrease
1160 Sound/Keyclick Volume Up
1161 Sound/Keyclick Volume Down
1172 Keyclick On
1173 Keyclick Off
1176 Sounds On
1177 Sounds Off
1822 Panel Tracking Enabled
* Only applies to the LC-1000.
Uploading and Upgrading
Assuming a PC is properly connected to the entire system, Crestron programming
software allows the programmer to upload programs and projects to the system and
touchpanel after their development. However, there are times when the files for the
program and projects are compiled and not uploaded. Instead, compiled files may be
distributed from programmers to installers, from Crestron to dealers, etc. Even
firmware upgrades are available from the Crestron website as new features are
developed after product releases. In those instances, one has the option to upload via
the programming software or to upload and upgrade via the Crestron Viewport.
NOTE: Currently, the Crestron Viewport is only available as a pull-down command
from SIMPL Windows and VT Pro-e (Tools | Viewport). The Viewport utility
accomplishes multiple system tasks, primarily via an RS-232 or TCP/IP connection
between the control system and a PC. It is used to observe system processes, upload
new operating systems and firmware, change system and network parameters, and
communicate with network device consoles and touchpanels, among many other
tasks. Viewport can also function as a terminal emulator for generic file transfer. All
of these functions are accessed through the commands and options in the Viewport
menus. Therefore, for its effectiveness as a support and diagnostic tool, the Crestron