Specifications
Crestron CSA-PWS10S-HUB Power Supply for Crestron Shade Motors
Wiring
Once the unit is properly secured to the mounting surface, the unit must be properly wired. Refer to the guidelines
below for details.
CAUTION: All power feeds must be protected by single pole listed circuit breaker or branch rated fuse no greater
than 20 A.
NOTE: Use copper conductors only—rated 75°C or better.
NOTE: All wiring must be installed in accordance with all local and national electrical codes.
NOTE: Four snap bushings are supplied. If required, insert the snap bushings into the knockouts at the bottom of
the enclosure to prevent damage to low voltage wiring.
The device must be mounted before operation.
Class 1 and Class 2 field wires must be kept separate. Refer to the following illustrations showing wiring details.
Areas for high voltage (Class 1) wiring are along the left side of the unit. The right side of the enclosure is reserved
for low voltage (Class 2) wiring.
NOTE: The installer must provide disconnect means within site of the enclosure.
NOTE: The CSA-PWS10S-HUB power cable is considered to be a disconnect means. For this reason the total
length of power cable from CSA-PWS10S-HUB to the outlet cannot exceed 14 feet (4.5 meters).
Class 1 Wiring Details
Class 1 Wiring
WIRE CONNECTION COLOR
GND Ground Green with Yellow Stripe
NEUT Neutral White
LINE Hot Black
Class 2 Wiring Details
Neutral, Line,
and Ground
Connections
Class 1
Wiring Only
Power
From
120-240
Vac
Class 2
Wiring Only
10 • Power Supply for Crestron Shade Motors: CSA-PWS10S-HUB Installation Guide – DOC. 7438C