Specifications
infiNET™ SWITCHES
RF Exposure (OET Bulletin 65)
To comply with FCC's RF exposure limits for general
population / uncontrolled exposure, this transmitter must
be installed to provide a separation distance of at least 20
cm from all persons and must not be co-located or
operating in conjunction with any other antenna or
transmitter.
Industry Canada Statement
The term "IC" before the certification/registration number
only signifies that the Industry Canada technical
specifications were met.
IC: 5683A-CWD1011
Important Notes
Read before installation.
• Codes: Install in accordance with all local and
national electrical codes.
•
CAUTION: TO REDUCE THE RISK OF
OVERHEATING AND POSSIBLE DAMAGE
TO OTHER EQUIPMENT, DO NOT INSTALL
TO CONTROL A RECEPTACLE.
• Wiring: Use copper wire only. For supply
connection, use wires rated for at least 75°C.
• Load Type: The -SW1RF, -SW4RF, -SWS1RF,
-SWS4RF, and -SLVS1RF are designed for use
with permanently installed incandescent,
fluorescent (non-dimmable), low voltage,
neon/cold cathode, HID, ceiling fan, or tungsten
halogen lighting.
• Temperature: The -SW1RF, -SW4RF,
-SWS1RF, -SWS4RF, and -SLVS1RF are
designed to be used where temperatures are
between 32° to 104°F (0° to 40°C).
• Wallboxes: Devices mount in standard
wallboxes. For easy installation, Crestron
recommends using 3 ½” deep wallboxes. Several
devices can be installed in one wall box
(multigang). This requires the removal of side
sections (refer to diagram in next column) and
the derating of the switching device. For a
smooth appearance, one-piece multigang
faceplates (not supplied) can be installed.
• Other Switch Devices: Mechanical 3- or 4-way
switches will not work with the -SW1RF,
-SW4RF, -SWS1RF, -SWS4RF, and -SLVS1RF.
• Spacing: If mounting one device above another,
leave at least 4 ½” vertical space between them.
Multigang Installations
In multigang installations, several controls are grouped
horizontally in one wallbox. For a smooth appearance,
one-piece multigang faceplates (not supplied) can be
installed.
1. When combining controls in a wallbox, remove
inner side sections prior to wiring (refer to the
following figure).
Inner Sections of Multiganged Switches
(CLW-SW4RF Shown)
REMOVE INNER SECTIONS
DO NOT REMOVE OUTER SECTIONS
RUN
SET OFF
RUN
SET OFF
The load capacity must also be derated. The
following charts provide derating information for
various applications.
Derating Information for Incandescent, Tungsten Halogen,
and Electronic Low Voltage Applications
Part Number No Side
Removed
One Side
Removed
Two
Sides
Removed
-SW1RF/
-SW4RF
1000W 700W 550W
-SWS1RF/
-SWS4RF
1000W 700W 550W
-SLVS1RF No Derating Necessary
Derating Information for Magnetic Low Voltage and
Neon/Cold Cathode Applications
*
Part Number No Side
Removed
One Side
Removed
Two Sides
Removed
-SW1RF/
-SW4RF
1000VA/
750W
700VA/
500W
550VA/
400W
-SWS1RF/
-SWS4RF
1000VA/
750W
700VA/
500W
550VA/
400W
-SLVS1RF No Derating Necessary
* VA ratings are for input power to the transformer. If you do not
know the input power requirement of the transformer, use the bulb’s
wattage rating to determine proper rating.
4 • infiNET™ Wall Box Switch : CLW-SW1/4RF, SWS1/4RF, & SLVS1RF Installation Guide - DOC. 6293C