Installation
Important Notes (Read Before Installation)
• Codes: Install in accordance with all local and national electrical codes.
• Wiring: Use copper wire only. For supply connections, use wires rated for at least 75°C.
• Lighting Load Types: LED, incandescent, magnetic low-voltage, neon/cold cathode, 2-wire dimmable
fluorescent, and non-dim lighting.
Electronic low-voltage, 3 and 4-wire fluorescent, high-inrush switching, and 277 V via CLS-EXP Series
expansion modules (sold separately).
• Temperature: The iLux units are designed for use where temperatures are between 0° to 40° C (32° to
104° F).
• Electrical Boxes: The iLux units mount in standard 4-gang electrical boxes, 89 mm (3 1/2 inches) deep,
minimum.
• Make certain that power is turned off, and ensure that there is at least 115 mm (4 1/2 inches) of open
space above and below the electrical box location to permit adequate heat dissipation.
Label Load Type Symbol Definition
SYMBOL DEFINITION
Incandescent lamps
Fluorescent lamps
Iron core transformer for extra low-voltage incandescent lamps
Electronic step-down converter for extra low-voltage incandescent lamps
Terminal for regulated load
WARNING: Turn off power at the distribution panel circuit breaker. Installing with power on can result in serious
personal injury and damage to the device.
CAUTION: To reduce the risk of overheating and possible damage to other equipment, do not use to control a
receptacle or a motor-operated appliance.
NOTE: The CLSI-C6 units require a neutral connection for operation. If no neutral is present, contact a licensed
electrician for installation.
The following tools and hardware are required for installation.
• A 4-gang electrical box (not supplied), 89 mm (3 1/2 inches) deep, minimum.
• Phillips torque screwdriver (not supplied)
• Four 22 mm (7/8 inch) pan head Phillips screws (supplied)
If the planned configuration includes connection to shade controllers, keypads, or a Crestron 2-Series control
system, the following items are also required.
• Cresnet network cable(s) (not supplied)
• Terminal block connector(s) (two supplied)
For detailed configuration options, refer to the latest version of the Crestron CLS/CLSI-C6 & CLS/CLSI-C6M iLux
Integrated Lighting System Operations Guide (Doc. 6347), which is available from the Crestron Web site
(
www.crestron.com/manuals).
Check that any required Cresnet wiring has been installed and verified. Then, use the following procedure to install
the iLux unit (CLSI-C6M is shown in the illustrations).