FUNCTION
NAME
TURN OFF SCENE LIGHTS (ON, 1–15)
Behavior Same as Recall Scene button, except
a) All lights affected by the scene go to off level.
b) Shades are not affected.
Note that the list of unaffected lighting loads and the fade
time are the same as for the Recall Scene function.
LED Flash while lights are fading, off when fade is done.
Applies To Remote Button
Rocker Behavior N/A
Notes N/A
FUNCTION
NAME
TOGGLE SCENE (ON, 1–15)
Behavior Alternates between “Recall Scene” and “Turn Off Scene
Lights” actions for the specified scene. In determining which
action should be executed, the CLS-C6 checks the state of
all lights programmed in the scene. If any light in the scene
is on, this function causes the lights to go off. If all lights in
the scene are off, this function recalls the scene.
LED Flash while lights are actively fading (either direction). On
when any light in scene is on, while not fading.
Applies To Standard Rocker, Shifted Rocker, Remote Button
Rocker Behavior If the “Enable Raise/Lower on Scene Recall Buttons” option
is set, then the right and left rockers perform “Scene Raise”
and “Scene Lower” functions, whether or not scene feedback
LED for that button is lit. To toggle the scene, center of
button must be pressed.
If the “Enable Raise/Lower on Scene Recall Buttons” option
is not set, then the right, left, and center press all perform the
same function.
Notes Toggle function intended only for scenes that do not affect
shades.
FUNCTION
NAME
RAISE LIGHTING LOAD (1–6)
Behavior The specified lighting load raises as long as the button is
held. It stops when button released. Rate is the global ramp
rate.
If they hit the high-end limit, the lights stop at that point, but
the bar graph display continues to rise. If going up from
OFF, lights immediately go to the low-end limit, and the bar
graph display starts rising from 0. When the display (i.e.: the
internal ramp value) reaches the low-end limit, the light start
moving up in sync.
For non-dim load, lights immediately go to full on.
LED On while button is pressed
Applies To Remote Button
Rocker Behavior N/A
Notes This is same as pressing the right side of front panel function
button when in Lights Mode.