Specifications

Crestron CLS/CLSI-C6 & CLS/CLSI-C6M iLux Integrated Lighting System
Operations Guide DOC. 6347G iLux Integrated Lighting System: CLS/CLSI-C6 & CLS/CLSI-C6M 65
Scene Toggle Command
The following command is used to toggle scene lights. Command is not supported
for Off scene:
Syntax: M SC [XX] [TOG]
XX = ON, 115 Scenes
Scene Turn Off Lights Command
The following command is used to turn off scene lights:
Syntax: [ILUX] SC [XX] OFF
XX = ON, 115 Scenes
Scene State Query Command
The following command is used to read scene states. This command is not supported
for slave CLS-C6 devices.
Syntax: M SC [XX|ALL] STATE ?
XX = OFF, ON, 115 Scenes
Reply packet:
M SC [XX] STATE [S]
S = 1/0 Scene state (1 means scene selected, 0 means scene not selected)
M SC [ALL] STATE [MASK]
MASK = Bit mask Bit0Bit16
(Bit0 = off scene state, Bit1 = On scene state,
Bit2Bit16 = Scene1Scene15)
Scene Programming
Commands
Scene Quick Save Command
This command is used to save current light levels for selected scene:
Syntax: [ILUX] SC [XX] SAVE
XX = ON, 115 Scenes
Scene Query Light Zone Level Command
This command is used to read light level in scenes. This command is not supported
for slave CLS-C6 devices.
Syntax: M SC [XX] LZLVL ?
XX = OFF, ON, 115 (Scenes)
Reply packet:
M SC [XX] LZLVL [LEVEL1] [….] [LEVEL6]
LEVELx = 0100 for light zone1 through light zone6