Specifications
Crestron CLS/CLSI-C6 & CLS/CLSI-C6M iLux Integrated Lighting System
Operations Guide – DOC. 6347G iLux Integrated Lighting System: CLS/CLSI-C6 & CLS/CLSI-C6M • 63
[ILUX] LZ ALL NAME [LABEL1], […], [LABEL6]
LABELx = Light zone names separated by comma
Shade Group Commands
Shade Group Operation
Commands
Shade Group Position Command
The following command is used to set shade group position:
Syntax: [ILUX] SZ [X|ALL] POS [LEVEL]
X = 1–6 Shade group
ALL = All Shade groups
LEVEL = 0–100
Shade Group Position Query Command
The following command is used to get shade group position. This command is not
supported for slave CLS-C6 controllers and is applicable for Somfy
®
shades only:
Syntax: M SZ [X|ALL] POS ?
Reply packet:
M SZ [X|ALL] POS [LEVEL1] [….] [LEVEL6]
LEVELx = 0–100 for shade group 1–6
Shade Group Open, Close, and Stop Command
The following command is used to open, close, or stop shade group(s):
Syntax: [ILUX] SZ [X|ALL] [OPEN|CLOSE|STOP]
X = 1–6 Shade group
ALL = All shade groups
Shade Group Jog Open and Close Command
The following command is used to jog open or jog close the shade group(s):
Syntax: [ILUX] SZ [X|ALL] [JOPEN|JCLOSE]
X = 1–6 Shade group
ALL = All shade groups
Shade Group Open/Stop/Close/Stop Command
The following command is used to stop shade if running, open shade if last operation
was closing, and close if last time operation was opening:
Syntax: [ILUX] SZ [X|ALL] [OSCS]
X = 1–6 Shade group
ALL = All shade groups
Shade Group Programming
Commands
Shade Group Name Query Command
The following command is used to query shade group name:
Syntax: [ILUX] SZ [X|ALL] NAME ?