Specifications
iLux Integrated Lighting System Crestron CLS/CLSI-C6 & CLS/CLSI-C6M
62 • iLux Integrated Lighting System: CLS-C6/C6M & CLSI-C6/C6M Operations Guide – DOC. 6347G
ALL = All light zones
Reply packet:
[ILUX] LZ [XX|ALL] MIN [LIMIT1] [….] [LIMIT6]
LIMITx = 0–100 (for light zone 1 through 6)
Light Zone Upper Limit Command
The following command is used to get light zone maximum limit. This command is
not supported for slave CLS-C6 controllers:
Syntax: M LZ [X|ALL] MAX ?
X=1–6 light zone
Reply packet:
M LZ [X|ALL] [MAX] [LIMIT1] [….] [LIMIT6]
LIMITx = 0–100 (for light zone 1 through 6)
Light Zone Load Type Command
The following command is used to get load types. This command is not supported
for slave CLS-C6 controllers:
Syntax: M LZ [X|ALL] TYPE ?
X=1–6 light zone
Reply packet:
M LZ [X|ALL] TYPE [CODE1] [….] [CODE6]
CODEx = refer to table below (type code for light zone through 6):
Light Zone Load Type Codes
SUPPORTED
TYPES CODE
DESCRIPTION
0 Unused
1 Non-dim
2 Incandescent
3 Magnetic low voltage
4 Cold Cathode
5 Fluorescent 2 wire
6 Fluorescent 3 wire
7 Fluorescent 0-10 V
8 Electronic Low Voltage
Light Zone Name Query Command
The following command is used to read light zone name:
Syntax: [ILUX] LZ [X|ALL] NAME ?
X=1–6 light zone
Reply packet:
[ILUX] LZ [X] NAME [LABEL]
LABEL = Light zone name